| 2009-07-17 17:06:10 | |
| | ** DENIED REVISION ** |
| | |
| | ** ELECTRICAL PERMIT ISSUED TO DATE IS ONLY FOR |
| | ELECTRICAL CONDUITS IN SLAB. |
| | |
| | ** SEPARATE PERMIT(S) STILL REQUIRED FOR LV. |
| | |
| | 1) NOTE: PLANS SHALL BE REVISED, SIGNED, DATED AND |
| | SEALED BY THE ENGINEER OF RECORD. |
| | FS 471 |
| | PLEASE ALSO SEE FAC 61G15-23.002 FOR MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCKS. THE PRINTED LICENSE NUMBER |
| | AS WELL AS CERTIFICATE OF AUTHORIZATION NUMBER PER FS |
| | 471.023. |
| | |
| | 2) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT |
| | PROTECTION SHOWN ON PANEL FEEDING TRANSFORMER EXCEEDS |
| | THE 125% PERMITTED. ONLY IF MEETING NOTE #5 CAN THIS BE |
| | DONE. |
| | IF MEETING NOTE #5 SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | ON THIS SPECIALIZED TYPE OF TRANSFORMER. |
| | 110.3, 90.7 |
| | |
| | 3) NOTE: THE NOTE ON THE PLANS FOR THE LIGHTING |
| | CONTROLS DOES NOT MEET FBC 13-415.1.AB.1.1,.1.2, .1.3 |
| | OR .1.4. SEE THE FOLLOWING NOTES BELOW: |
| | A) ZONES, AND OVER RIDES PER SECTIONS GIVEN ARE NOT |
| | SHOWN ON PLANS. |
| | |
| | B) OVER RIDES FOR THE OCCUPANTS AND MAXIMUM OVER RIDE |
| | TIMES ARE NOT SHOWN. |
| | |
| | C) THE SYMBOL LEGEND ONLY INDICATES STANDARD SINGLE |
| | POLE SWITCHES FOR ALL SEPARATE SPACES. THESE ARE NOT |
| | PERMITTED AND DO NOT MEET THE MINIMUM FBC REQUIREMENTS. |
| | |
| | D) THE PLANS INDICATE STANDARD SINGLE POLE SWITCHES FOR |
| | OUTSIDE LIGHTING CONTROLS WHICH ARE NOT PERMITTED. |
| | PLEASE SEE 13-415.1.AB.1.4 AS ONE OF THE TWO TYPES OF |
| | CONTROLS MEETING MINIMUM IS REQUIRED. |
| | |
| | 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE |
| | CALCULATIONS DO NOT MEET THE MINIMUM PER FBC |
| | 13-415.AB.5. ALL FIXTURES, THE NUMBER OF FIXTURES, THE |
| | TYPES OF FIXTURES ETC SHALL BE SPECIFIC ON THE INPUT |
| | DATE REPORT. IT IS NOT PERMITTED TO STATE FOR EXAMPLE * |
| | 1-FIXTURE AT 3500 WATTS*. |
| | ALSO THE FIXTURES SHALL BE SPECIFIC. PLANS MAY NOT ONLY |
| | STATE FOR EXAMPLE A *2X4 FLUORESCENT FIXTURE*. THERE |
| | ARE FIXTURES WITH MANY POWER FACTORS RATINGS WHICH WILL |
| | HAVE AN AFFECT ON THE CALCULATIONS. THERE ARE ALSO THE |
| | SAME TYPE OF FIXTURES WHICH COULD BE 2LT, 3LT OR 4LT. |
| | THIS IS THE NSAME |
| | THERE ARE OTHER EXAMPLES ON THE IDR THAT DO NOT MINIMUM |
| | REQUIRED. |
| | THE TOTAL ON THE IDR AND SUMMARY DO NOT COORDINATE WITH |
| | THE PLANS. |
| | THE CODE TABLE REFERENCED ON PLANS IS NOT IN THE FBC |
| | SECTION NOTED ABOVE FOR THE LIGHTING PERFORMANCE |
| | LEVELS. |
| | |
| | 5) NOTE: THE TRANSFORMER IS A SEPARATELY DERIVED |
| | SYSTEM. THE RISER INDICATES A NEUTRAL CONDUCTOR FROM |
| | THE 277/480V PANEL TO THE TRANSFORMER. THIS IS NOT |
| | PERMITTED. |
| | 250.6,250.20,250.30 ETC |
| | |
| | 6) NOTE: PLEASE SEE 250.20,250.30,250.50, AS THE PLANS |
| | STATE THE GEC TO CWP AND GROUND ROD FOR TRANSFORMER |
| | ATTACHMENT. HOWEVER PER SECTIONS ABOVE, BUILDING STEEL |
| | IS REQUIRED. PLEASE ALSO SEE 250.56 FOR RESISTANCE |
| | REQUIRED. |
| | |
| | 7) NOTE: SHOW WINDOW LOADS NEED TO BE SHOWN PER 220.14, |
| | 220.43 |
| | |
| | 8) NOTE: CIRCUITING FOR EMERGENCY AND EXIT LIGHTS SHALL |
| | BE SHOWN PER 700.12F |
| | (SHALL BE CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT). |
| | |
| | 9) NOTE: PLEASE VERIFY SIGN CIRCUIT VOLTAGE DROP |
| | SHOWING 3-#6 CONDUCTORS? THIS IS NOT A CODE VIOLATION |
| | HOWEVER IF PLANS INDICATE #6 THEN THIS MUST BE |
| | INSTALLED. PLEASE CALL TO GO OVER. |
| | |
| | 10) NOTE: MAINS FOR BUILDING SHALL BE LABELED. 230.2E, |
| | 230.70,230.71,230.72. PLEASE SHALL LOCATIONS OF ALL |
| | MAINS. |
| | |
| | 11) NOTE: PLANS STATE 2007 EDITION OF THE FBC HOWEVER |
| | THE CODE IN ADOPTION BY FS 553.73 AS OF MARCH 1ST , |
| | 2009 IS THE 2007 FBC WITH THE 2009 SUPPLEMENTS. THIS IS |
| | IMPORTANT AS THE 2009 GLITCH REVISIONS TO THE 2007 FBC |
| | SUBSTANTIALLY REVISED MOST IF NOT ALL OF CHAPTER 13 |
| | ALONE. |
| | |
| | 12) NOTE: THE PANEL ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER DOES NOT INDICATE ANY MAIN. ALL TAPPED |
| | CONDUCTORS SHALL TERMINATE IN OVER CURRETN PROTECTION. |
| | 240.21. PLEASE ALSO SEE 408.36, 240.4, 310.16 ETC |
| | |
| | *** AS THERE ARE SOME ITEMS NOT YET SUBMITTED THERE MAY |
| | BE NEW COMMENTS WHICH MAY FOLLOW. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |