| Date |
Text |
| 2009-04-08 18:21:26 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. THE SEAL FOR THE ARCHITECT DOES NOT IMPRESS ALL |
| | INFORMATION REQUIRED BY FAC 61G1-16.001 & |
| | 61G1-16.002(2) & FS 481.2055. PLEASE RESEAL ALL SHEETS |
| | WHICH DO NOT IMPRESS THE REQUIRED INFORMATION. |
| | |
| | 2. SHT A-8 ADA BATHROOM CLEARANCE PLAN. THE LAVS SHALL |
| | NOT BE IN THE CLEAR FLOOR SPACE FOR THE WATER CLOSETS. |
| | SEE FIGURE 11-30E. LAVS SHALL BE A MINIMUM 15" OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON |
| | THE 30" DIMENTION OF THE CLEAR FLOOR SPACE REQUIRED FOR |
| | THE LAV. PLEASE INDICATE ON PLANS. |
| | |
| | 3. SHT A-8 DETAIL FOR THE W/C GRAB BARS DOES NOT SHOW |
| | THE GRAB BAR LENGTH BEHIND THE WATER CLOSET. MINIMUM 36 |
| | INCH GRAB BAR IS REQUIRED, SECTION 11-4.16.4. PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 4. SHT P-4 WATER ISOMETRIC RISER DIAGRAM SHOW WHAT |
| | APPEAR TO BE AIR CHAMBERS AT EACH FIXTURE. AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE. SECTION 604.9 WATER |
| | HAMMER ARRESTORS ARE REQUIRED ONLY ON QUICK CLOSING |
| | VALVES AND SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING IF USED. PDI-WH |
| | 201. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |