2009-03-31 13:37:14******PROVISO******
 1. OUTDOOR APPLIANCES (ROOFTOP UNITS) SHALL BE DESIGNED
 AND INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH
 FBC-M 301.12. PROVIDE DATA SHOWING UNITS AR3E DESIGNED
 FOR WIND RESISTANCE PRIOR TO MECHANICAL INSPECTION.
  
 2. PROVIDE DETAIL WITH SUPPORTING WIND LOAD
 CALCULATIONS FOR ATTACHMENT OF RTU AND CURB IN
 ACCORDANCE WITH FBC-M 301.12.
  
 3. RTU DETAIL ON M-2 SHOWS FLOAT SWITCH OUTSIDE UNIT IN
 THE PRIMARY DRAIN LINE. ON DOWN-FLOW UNITS THE
 WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE
 THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  