| Plan Review Notes For Permit 09030496 |
| Permit Number |
09030496 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-31 13:37:14 | ******PROVISO****** | | | 1. OUTDOOR APPLIANCES (ROOFTOP UNITS) SHALL BE DESIGNED | | | AND INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH | | | FBC-M 301.12. PROVIDE DATA SHOWING UNITS AR3E DESIGNED | | | FOR WIND RESISTANCE PRIOR TO MECHANICAL INSPECTION. | | | | | | 2. PROVIDE DETAIL WITH SUPPORTING WIND LOAD | | | CALCULATIONS FOR ATTACHMENT OF RTU AND CURB IN | | | ACCORDANCE WITH FBC-M 301.12. | | | | | | 3. RTU DETAIL ON M-2 SHOWS FLOAT SWITCH OUTSIDE UNIT IN | | | THE PRIMARY DRAIN LINE. ON DOWN-FLOW UNITS THE | | | WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE | | | THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M | | | 307.2.3.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|