| 2009-04-09 12:38:39 | *****DENIED***** |
| | |
| | 1. ON SHEET A-2 UNDER APPLICABLE CODES, AMEND CODES TO |
| | CURRENT EDITIONS SUCH AS: 2006 NFPA 101 AND FLORIDA |
| | FIRE PREVENTION CODE 2007. |
| | |
| | 2. ON SHEET A-5, AMEND NOTES TO REFLECT CURRENT CODES |
| | SUCH AS: NFPA 101 (2006 EDITION), FLORIDA FIRE |
| | PREVENTION CODE (2007 EDITION), AND NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 3. ON SHEET A-7, INDICATE IN DOOR SCHEDULE WHICH DOORS |
| | ARE TO BE FIRE RATED AND HAVE DOOR CLOSERS (SEE DOOR #3 |
| | - MECHANICAL ROOM & DOOR #6 - JANITOR'S CLOSET. PLEASE |
| | BE ADVISED THAT FIRE DOORS AND WINDOWS SHALL COMPLY |
| | WITH NFPA 80 - 1999 EDITION. |
| | |
| | 4. ON SHEET E-3, AMEND GENERAL ELECTRIC NOTES (NOTE #1) |
| | TO REFLECT NFPA 70 - 2005 EDITION AND NFPA 101 - 2006 |
| | EDITION. |
| | |
| | 5. LIST THE OCCUPANCY TYPE (I.E. BUSINESS, MERCANTILE, |
| | ASSEMBLY) AND OCCUPANT LOAD FOR THIS PROPOSED PROJECT |
| | SITE. |
| | |
| | 6. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE |
| | PROPOSED PROJECT SITE. |
| | |
| | 7. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS |
| | IN TERMS OF CLASS A OR CLASS B. |
| | |
| | 8. SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES IN |
| | TERMS OF CLASS I OR CLASS II. |
| | |
| | 9. BE ADVISED THAT CITY HALL (FORMERLY 200 2ND STREET) |
| | IS CURRENTLY ADDRESSED/LOCATED AT 401 CLEMATIS STREET, |
| | WEST PALM BEACH, 33401. AMEND JURISDICTIONAL AUTHORIES |
| | INFORMATION ON THE COVER SHEET. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |