| Plan Review Notes For Permit 09030472 |
| Permit Number |
09030472 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-07 19:19:50 | ** | | | ACESS CONTROLS ARE UNDER SEPARATE PLANS AND PERMITS. | | | LOW VOLTAGE SYSTEMS SHOWN UNDER SEPARATE PERMIT HOWEVER | | | MAY REFERENCE MAIN PERMIT FOR TURN AROUND PERMIT. | | | THE IDF ROOM IS NOT AN IT ROOM PER NEC 645.4. IF ANY | | | WIRING METHODS FROM NEC 645 ARE USED, THEN ALL ITEMS | | | LISTED UNDER 645.4 1-5 MUST BE MET. |
|