 ACESS CONTROLS ARE UNDER SEPARATE PLANS AND PERMITS.
 LOW VOLTAGE SYSTEMS SHOWN UNDER SEPARATE PERMIT HOWEVER
 MAY REFERENCE MAIN PERMIT FOR TURN AROUND PERMIT.
 THE IDF ROOM IS NOT AN IT ROOM PER NEC 645.4. IF ANY
 WIRING METHODS FROM NEC 645 ARE USED, THEN ALL ITEMS
 LISTED UNDER 645.4 1-5 MUST BE MET.