Plan Review Notes
Plan Review Notes For Permit 09030472
Permit Number 09030472
Review Stop P
Sequence Number 1
Notes
Date Text
2009-03-31 06:57:44DENIED
 REFERENCE:
 FBC-2007 PLUMBING W/2009 SUPPLEMENTS
 FBC-2007 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE WATER CLOSET SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 *NOTE: WATER CLOSET SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. FIG. 28. PLEASE INDICATE ON
 PLANS.
  
 2. SHTS A1.0 & A5.1 (DETAIL 26 FOR THE PANTRY SINK)
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED, CABINET DOORS NOT APPROVED IN CLEAR FLOOR
 SPACE).
 C. 11-4.24.5 EXPOSED PIPES & SURFACES
  
 3. SHTS P2-1 KEY NOTE 4 & P3.1 SANITARY ISOMETRIC. PER
 712.2 A CHECK VALVE & A FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED IN
 THE PUMP DISCHARGE PIPING BETWEEN THE PUMP AND THE
 GRAVITY DRAINAGE SYSTEM. PLEASE SHOW ON PLANS.
  
 4. SHTS P2.1 & P3.1 SANITARY ISOMETRIC SHOW THE
 CONNECTION OF TO THE MAIN VENT LINE FOR THE W/C-1.
 SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  