| 2009-03-25 19:08:09 | *****PROVISO***** | | | SEE REDLINED NOTES ON PLANS FOR THE FOLLOWING | | | CONDITIONS: | | | | | | 1. PAGE M0.1: GENERAL NOTE #3 CONTAINS AN INCORRECT | | | CODE REFERENCE. UPDATE CODE REFERENCE TO REFLECT | | | CHANGES TO THE 2007 FBC, WHICH TOOK EFFECT ON MARCH 1, | | | 2009. THE PRESCRIPTIVE INSTALLATION METHOD REFERENCED | | | IN FBC-M301.13.1 (2004 EDITION) ARE NO LONGER | | | APPLICABLE IN THE 2007 FBC-M. ENGINEERING IS REQUIRED | | | FOR ALL WIND RESISTANT INSTALLATIONS. SEE FBC-M 301.12. | | | | | | 2. PAGE M0.1: GENERAL NOTE #29 CONTAINS AN INCORRECT | | | CODE REFERENCE. THE REQUIREMENT IS THE SAME, BUT THE | | | CORRECT CODE SECTION IS NOW FBC-B 13-410.AB.4.2. UPDATE | | | CODE REFERENCE TO REFLECT CHANGES TO THE 2007 FBC, | | | WHICH TOOK EFFECT ON MARCH 1, 2009. | | | | | | 3. PAGE M0.1: GENERAL NOTE #32 CALLS FOR WIND LOAD | | | CALCULATIONS AND INSTALLATION DETAILS TO BE PROVIDED BY | | | STRUCTURAL ENGINEER/ARCHITECT. NO SUCH INFORMATION WAS | | | PROVIDED. | | | | | | REVISE PLANS TO ADDRESS THE ABOVE ISSUES PRIOR TO | | | MECHANICAL INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|