| 2009-03-26 19:57:22 | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: THE SEAL ON THE ARCHITECTURAL PLANS DOES NOT |
| | MEET FLORIDA ADMINISTRATIVE CODE 61G1-16.002 FOR |
| | CORRECT TYPE OF SEAL. THE INITIAL RULING OF A 2INCH |
| | SEAL WAS ADOPTED IN 1989. THIS HAS SINCE BEEN UPDATED |
| | HOWEVER HAS BEEN A REQUIREMENT SINCE THAT DATE. AS THIS |
| | REVIEWER MAY BE THE LAST TO ISSUE PLANS FOR PERMIT THIS |
| | IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | THE ARCHITECT MAY COME INTO OFFICE AND RE-SEAL PLANS |
| | WITH CORRECT SEAL. |
| | |
| | 2) NOTE: PLEASE SEE FAC 69A-60.003 AND .004 AS THE 2006 |
| | NFPA-101 LIFE SAFETY CODE AND 2006 NFPA-1 HAS BEEN |
| | ADOPTED SINCE DECEMBER 31ST 2008. THE 2007 FBC HAS ALSO |
| | SINCE ADOPTED THESE AS OF MARCH 1ST, 2009. |
| | |
| | 3) NOTE: PLEASE PROVIDE NOTES FOR ACCESS CONTROL |
| | DEVICES/CLARIFY THE EGRESS WHICH SHALL NOT BE IMPEDED |
| | UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE |
| | NFPA-101 CHAPTER 7.2.1.5, 7.2.1.6.2 |
| | PLEASE PROVIDE INFORMATION ON DEVICES. |
| | PLEASE KNOW SEPARATE PERMITS ARE REQUIRED FOR LOW |
| | VOLTAGE SYSTEMS. THIS MAY BE REMOVED FROM SETS OF PLANS |
| | AND BROUGHT BACK IN UNDER SEPARATE PERMIT. |
| | IF ALL LOW VOLTAGE SYSTEMS ARE LEFT IN SETS ONCE OK |
| | WITH REVIEWS, THEN THE SUB CONTRACTORS FOR LOW VOLTAGE |
| | WORK WILL BE ONLY REQUIRED TO REFERENCE PLANS FOR MAIN |
| | BUILDING PERMIT. AT THAT TIME A TURN AROUND PERMIT WILL |
| | BE ISSUED. |
| | |
| | 4) NOTE: PLANS INDICATE THE CU ON ROOF HOWEVER PLEASE |
| | INDICATE IF THERE IS GOING TO BE A NEW OR EXISTING GFI |
| | AS REQUIRED PER 210.8B3, 210.63 |
| | |
| | 5) NOTE: AS THE IDF ROOM DOES NOT THE MINIMUM |
| | REQUIREMENTS OF NEC 645.4 PLEASE PLACE NOTE ON PLANS |
| | WHICH STATES |
| | * NO WIRING METHODS PERMITTED IN NEC 645 IS PERMITTED*. |
| | BASED ON PLANS THIS IS NOT AN IT AND THE CODE DOES NOT |
| | PERMIT ANY OF THE LESS STRINGENT WIRING METHODS IN 645. |
| | FOR INFORMATION; IT PERSONNEL MAY WANT TO BE CONSULTED |
| | ON WIRING METHODS INTENDED. IF RATING THE ROOM AND |
| | OTHER ITEMS LISTED IN 645.4 IS DONE AT THIS TIME THEN |
| | WIRING METHODS IN 645 WOULD BE PERMITTED. |
| | |
| | 6) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE PROPOSED UPS. PLEASE BE SURE PAPERWORK CONTAINS |
| | THE REQUIRED LISTING FROM A NRTL. (NATIONALLY |
| | RECOGNIZED TESTING LABORATORY). |
| | 110.3. 90.7 |
| | FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION NEEDED. |
| | |
| | 7) NOTE: PLEASE PLACE NOT ON PLANS FOR REQUIRED SIGNAGE |
| | AT ROOM/AREA 1418 FOR PANELS 2H AND 3L. NO STORAGE |
| | PERMITTED* ELECTRICAL CLOSET* OR WORDS TO THAT AFFECT. |
| | 110.26, 240.24, |
| | |
| | 8) NOTE: PLEASE RE-FIGURE LIGHTING PERFORMANCE |
| | CALCULATIONS AND COORDINATE WITH THE LIGHTING CONTROL |
| | PANEL LOADS. AN EXAMPLE IS CORRIDOR 1418. 465, ON PANEL |
| | 485 ON CALCULATIONS. |
| | |
| | 9) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OCP ON THE |
| | 45KVA TRANSFORMER IS 70AMPS UNLESS MEETING NOTE #3. IF |
| | TRANSFORMER MEETS NOTE #3, PLEASE PROVIDE INFORMATION |
| | OF THAT UNIT ON PLANS. |
| | IF NOT THE MAXIMUM OCP IS 125%. PLEASE ADJUST. |
| | |
| | 10) NOTE: PLEASE SEE PANEL 2H, THIS IS LISTED AS A |
| | 125AMP PANEL AND 42 CIRCUITS HOWEVER PANEL SCHEDULE |
| | ALSO LIST THIS PANEL AS 30POLES. |
| | PLEASE COORDINATE. THIS IS THE SAME TYPE OF COMMENT FOR |
| | 2UPS AND 1H. |
| | 110.3 |
| | |
| | 11) NOTE: PLEASE SEE PANEL 2L AS THIS IS SHOWN AS |
| | 150AMP MCB ON RISER AND 225AMP MLO ON SCHEDULE. |
| | THE OTHER PANELS SUCH AS 1L AND 3L LISTS BOTH MCB AND |
| | MLO ON PANELS PLEASE CLARIFY. MCB IS REQUIRED PER |
| | 240.21, 408.36 |
| | |
| | 12) NOTE: PLEASE SEE PANEL 2UPS, WHICH IS SHOWN AS |
| | 60AMP MCB AS REQUIRED ON RISER HOWEVER PANEL SCHEDULE |
| | LIST THIS AS MAIN LUG ONLY IN TWO LOCATIONS. |
| | THIS IS THE SAME FOR PANEL 1UPS ALSO. |
| | PLEASE COORDINATE AS REQUIRED. 106.1.1, 106.1.2 |
| | NEC 240.21 |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |