Plan Review Notes
Plan Review Notes For Permit 09030469
Permit Number 09030469
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-23 10:57:44*****DENIED*****
  
 1. THE ENTIRE INSTALLATION TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. PLEASE INDICATE WHAT EQUIPMENT THE NEW GENERATOR
 WILL SUPPLY. IS/ARE ANY EMERGENCY EQUIPMENT ( EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE ALARM SYSTEM, ETC.)
 BEING SUPPLIED POWER FROM THIS GENERATOR?
  
 3. EMERGENCY GENERATORS AND/OR STANDBY GENERATORS SHALL
 BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY
 GENERATORS.
  
 4. SHOW/DISPLAY DEVICES PLANNED TO PREVENT POSSIBLE
 COLLISION TO THE GENERATOR FROM PASSING VEHICLES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW