| Date |
Text |
| 2009-04-17 15:51:49 | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE: ALL PLANS SHALL CONTAIN THE MINIMUM CODES |
| | UNDER WHICH DESIGNED. |
| | PLEASE KNOW THAT ALL PROJECTS SUBMITTED AFTER MARCH |
| | 1ST, 2009 SHALL BE UNDER THE FOLLOWING CODES. |
| | 2007 FBC W/ 2009 AMENDMENTS |
| | 2002 NFPA-110 |
| | 2005 NFPA70 |
| | |
| | ** AS PLANS DO NOT INDICATE WHETHER OR NOT ANY LIFE |
| | SAFETY SYSTEMS ARE FED FROM THE NEW PROPOSED UNIT, SOME |
| | ITEMS CAN NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | PLEASE ALSO SEE 2006 NFPA-101 FOR MINIMUM REQUIREMENTS. |
| | FS 553.73 |
| | |
| | 2) NOTE: PLEASE SEE FS 471.003 AND 481.229. ANY |
| | PROJECTS UNDER THE EXEMPTION SHALL CONTAIN THE PRINTED |
| | NAME AND SIGNATURE OF THE PERSON UNDER WHICH LICENSE IS |
| | APPLIED FOR TAKING RESPONSIBILITY OF SAID PLANS. |
| | |
| | 3) NOTE: PLEASE SEE 250.6, 250.24 AS EQUIPMENT |
| | GROUNDING CONDUCTORS ARE NOT PERMITTED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 4) NOTE: PLEASE PROVIDE ANY INFORMATION FOR ANY 700-701 |
| | SYSTEMS. |
| | |
| | 5) NOTE: PLEASE BE AWARE OF COMMENTS WITH RESPECT TO |
| | SERVICE PLATFORMS, ACCESS, GUARD RAILS ETC. |
| | PLEASE BE AWARE OF COMMENTS REGARDING DERM APPROVAL FOR |
| | THE 1200 GALLON TANK. |
| | PLEASE BE AWARE OF COMMENTS WITH RESPECT TO MINIMUM |
| | ELEVATIONS AND SLAB INFORMATION. |
| | ** NO INFORMATION SUBMITTED OR SHOWN FOR MANY OF THE |
| | ABOVE ITEMS. |
| | PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR REQUIRED MINIMUM |
| | CODE COMPLIANCE. |
| | |
| | 6) NOTE: PLANS NEED TO BE COMPLETE AND SHOW SUFFICIENT |
| | DETAILS FOR MINIMUM CODES AS NOTED ABOVE. |
| | PLEASE SEE NFPA-110 , FBC CHAPTER 10, 27, AND NEC |
| | 700,701,702. |
| | ** THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |