Plan Review Notes
Plan Review Notes For Permit 09030469
Permit Number 09030469
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-09 17:25:36BUILDING PLAN REVIEW
 PERMIT: 09030469
 ADD: 3071 CONTINENTAIL DR.
 CONT: VAN'S ELECTRIC
 TEL: (561)584-1077
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 9/09
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1F) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) IT APPEARS THE INSTALATION OF THIS GENERATOR AND
 TANK ARE ON THE EXTERIOR OF THE BUILDING AND EXPOSED TO
 WIND. PLEASE PROVIDE THE WIND DESIGN CRITERIA. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2A). BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B). WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C) . WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3) THE PLAN INDICATES THE REUSE OF AN EXISTING SLAB.
 2702.1 INSTALLATION.
  
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING. PLANS INDICATE 1200 GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC
 BUILDING 1609.1.3.
  
 5) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 6) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 7) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.