| Plan Review Notes For Permit 09030460 |
| Permit Number |
09030460 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-10 16:09:55 | WIRING AS SHOWN ON PCITURES NOT PER NEC. | | | | | | ALL BOX FILL SHALL BE CORRECTED. BOXES SHOWN EXCEED | | | CUBIC SQ INCHES FOR BOXES SHOWN. | | | DEDICATED CIRCUITS SHALL BE CORRECTED. PICTURES SHAL | | | THE REQUIRED DEDICATED WASHER CIRCUIT ON WITH OTHER | | | RECEPTACLES WHICH IS NOT PERMITTED. | | | WIRING METHODS FOR STRAPING AND INSTALLATION OF | | | PROTECTION OF CONDUCTORS PER NEC 300 SHALL BE CORRECTED | | | PROTECTION FROM GALVANIC REACTION REQUIRED |
|