| Plan Review Notes For Permit 09030430 |
| Permit Number |
09030430 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-24 18:31:17 | *****PROVISO***** | | | 1. SIZE OF DUCT AND FIRE DAMPER AT TRANSFER SOUND BOOTS | | | NOT LEGIBLE ON PLANS. REVISE PLAN TO SHOW DUCT SIZE | | | PRIOR TO INSPECTION. FBC-M 603.3, FBC-B 106.1.1 | | | | | | 2. PLANS SHOW FUTURE EXHAUST DUCT ROUTED IN CEILING | | | PLENUM. FUTURE EXHAUST CONFIGURATION SHALL NOT CREATE | | | POSITIVELY PRESSURIZED EXHAUST DUCT IN PLENUM IN | | | ACCORDANCE WITH FBC-M 601.5. | | | | | | SEE CORRESPONDING REDLINED NOTES ON PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|