Plan Review Notes
Plan Review Notes For Permit 09030430
Permit Number 09030430
Review Stop E
Sequence Number 1
Notes
Date Text
2009-03-24 17:50:35** PROVISO **
  
 1) NOTE: BATTERY BACK UP FIXTURES OF SOME SORT FOR
 MINIMUM EGRESS LIGHTING LEVEL OF 1FT CANDLE (AVERAGE)
 IS REQUIRED. THESE NEED TO BE CIRCUITED PER 700.12F TO
 LOCAL LIGHTING CIRCUIT IN AREA.
 THIS INCLUDES LOBBY, CORRIDORS AND BATH ROOM AREAS.
 AT THIS POINT IF A SINGLE MEANS OF OVER CURRENT
 PROTECTION WOULD TRIP UNDER NORMAL OR EMERGENCY
 CONDITIONS THERE WOULD BE EGRESS AREAS IN TOTAL
 DARKNESS.
 7.8.1.32, 7.9.1.2, .2.2.
 FBC 1006.1.2
 PLEASE REVISE
  
  
 2) NOTE: ALL ILLUMINATION FOR EMERGENCY LIGHTING
 CONTROL BY OCCUPANCY SENSOR TYPE DEVICE NEEDS TO MEET
 FBC 1006.1.2, NFPA-101 7.8.1.2.2 WHICH REQUIRES DEVICE
 TO BE "FAIL SAFE ON".
 PLEASE REVISE.
  
 3) NOTE: *** FOR INFORMATIONAL PURPOSE. PLEASE SEE
 ASTME-17 FOR REQUIRED MINIMUM FC LEVELS AT THE FLOOR AT
 ELEVATOR SILLS/LANDINGS. THIS IS BASED ON THE STATE
 ELEVATOR CODE AND NOT PART OF THIS REVIEW. ( REQUIRES
 10FC MIN.)
  
 4) NOTE: PER FAC 69A-60.004 THE 2006 NFPA-101 WAS
 ADOPTED ON DECEMEBR 31ST 2008. PLANS INDICATE 2003
 EDITION, PLEASE REVISE.
  
 ** PLANS NEED TO BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION. ANY INSTALLATION NOT DONE PER PROVISO
 ISSUED ON PLANS MAY RESULT IN A DELAY OF PROJECT.
 PLEASE CALL IF THERE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  