Plan Review Notes
Plan Review Notes For Permit 09030390
Permit Number 09030390
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-03 11:11:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DECLARE GOVERNING CODE.
  
 2. DECLARE WIND DESIGN CRITERIA.
  
 3. INCLUDE THE NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THIS DESIGN.
  
 4. NO FOOTINGS ARE SHOWN. PLEASE PROVIDE CALCULATIONS
 TO SHOW THAT THE CONCRETE SLAB IS SUFFICIENT TO SUPPORT
 DEAD LOADS AND RESIST WIND LOADS. FBC R301.
  
 5. SPECIFY NAILING FOR EACH CONNECTOR OR PROVIDE SPEC
 SHEETS FOR EACH CONNECTOR (AVAILABLE ON INTERNET).
  
 6. SEVERAL SHEETS SUBMITTED WITH NO WAY TO IDENTIFY THE
 SHEETS (PAGE NUMBERS, DETAIL LABELS). THIS MAKES IT
 VERY DIFFICULT TO REFER TO SPECIFIC SHEETS OR DETAILS
 FOR PLAN REVIEW. PLEASE ADDRESS.
  
 7. SEE FBC*109, ARCHITECTURAL QUALITY PLANS REQUIRED.
 PLANS ARE TO BE TO SCALE, DIMENSIONED, AND SUFFICIENT
 CLARITY TO SHOW SCOPE OF WORK.
  
 8. DETAIL SHOWS BOTTOM OF 4X4 AT THE TOP OF A 2"
 TOPPING, BUT MANUFACTURER INFORMATION SHOWS THE POST
 RAISED. IS THE ANCHOR EMBEDDED IN THE CONCRETE? PLEASE
 REVISE DRAWING TO CORRECTLY DEPICT PROPOSED WORK OR
 PROVIDE INFORMATION FROM THE MANUFACTURER WHICH ALLOWS
 THE ANCHOR TO BE EMBEDDED AND THE RAISED POST AT
 FINISHED FLOOR LEVEL.
  
 9. PROVIDE A DETAIL, FOUNDATION THROUGH THE ROOF, TO
 SHOW HOW THIS PROPOSED IMPROVEMENT WILL BE STRUCTURALLY
 CONTINUOUS FBC R301.
  
 10. THE ROOF PRODUCT APPROVAL SUBMITTED IS AN
 UNDERLAYMENT WHICH CANNOT BE EXPOSED LONGER THAN 180
 DAYS. HOW LONG AGO WAS THIS PRODUCT INSTALLED?
  
 11. IT APPEARS THAT THE PROPOSED IMPROVEMENT IS
 ATTACHED TO FASCIA BOARD. FASCIA IS NOT A STRUCTURAL
 COMPONENT; THIS CANNOT BE USED TO SUPPORT THE PROPOSED
 IMPROVEMENT. PLEASE SHOW HOW THIS WILL RESIST LOADS,
 FBC R301.
  
 12. IT IS NOT CLEAR HOW THIS HAS BEEN DESIGNED; SEE FBC
 R301.1. IF WFCM WAS USED, PLEASE PROVIDE COPIES OF THE
 PERTINENT CHARTS AND DETAILS TO SHOW THAT THIS PROPOSED
 IMPROVEMENT CAN WITHSTAND DESIGN LOADS. IF ASCE7 WAS
 USED, PLEASE PROVIDE CALCULATIONS FOR ALL STRUCTURAL
 ELEMENTS. FOR INSTANCE, 7 4X4 POSTS WERE SHOWN TO
 SUPPORT A 176 SF STRUCTURE. 2X4 RAFTERS, WITH NO
 SPACING SHOWN, ARE PROPOSED WITH A 9'7" SPAN. PROVIDE
 ALL STRUCTURAL DETAILS, SIZE, SPACING, AND CALCULATIONS
 IF PRESCRIPTIVE DESIGN HAS NOT BEEN IMPLEMENTED FBC
 R301.
  
 13. ROOF FRAMING PLAN, SPECIFY ROOF FRAMING SPACING. IT
 APPEARS THAT THERE MAY BE AN INTERMEDIATE SUPPORTING
 MEMBER IN THE MIDDLE OF THE 9'7" SPAN; THIS SHOULD BE
 SHOWN ON THE ROOF FRAMING PLAN IF IT EXISTS. IF THERE
 IS AN INTERMEDIATE SUPPORT, IT APPEARS THAT IT SPANS
 14'2"; PROVIDE EVIDENCE (CALCULATIONS OR PRESCRIPTIVE
 DESIGN FROM WFCM) THAT THIS COMPLIES WITH DESIGN
 CRITERIA, SEE OTHER COMMENTS.
  
 14. SPECIFY NAILING PATTERN FOR ROOF SHEATHING.
  
 15. A ROOF PERMIT WILL BE REQUIRED. FOR FLAT DECKS,
 CONTRACTOR IS TO INDICATE WHICH APPROVED ASSEMBLY WILL
 BE USED AND SPECIFY ENHANCED FASTENING FOR CORNER AND
 PERIMETER ZONES IF REQUIRED. FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FAC9B72 FOR ROOF COVERING.
  
 16. SPECIFY ROOF SLOPE; NONE SHOWN FBC R CHAPTER 9. AS
 ROOF TYPE AND PRODUCT HAS NOT BEEN DETERMINED, A
 SPECIFIC CODE SECTION CANNOT BE PROVIDED.
  
 17. THIS PROPERTY RECEIVED A STOP WORK ORDER FOR
 ELECTRIC WORK PERFORMED WITHOUT A PERMIT. PLEASE
 ADDRESS THIS ISSUE AT THIS TIME OR ADVISE AS TO STATUS
 OF THIS ISSUE.
  
  
  
  
  