| Notes |
| Date |
Text |
| 2009-04-02 17:04:12 | ** DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE KNOW THAT PER FS 553.73: THE STATE OF | | | FLORIDA AS OF MARCH 31ST,2009 HAS ADOPTED THE 2007 FBC | | | WITH 2009 GLITCH AMENDMENTS. | | | THE PLANS SUBMITTED ARE UNDER 2004 FBC. | | | PLEASE ALSO SEE THE ELECTRICAL CODE REFERENCE ON PLANS | | | FOR GROUNDING IS FROM THE 1996 NEC. | | | THE CURRENT SECTION UNDER THE 2005 NEC IS NOT 250.95 | | | FOR EQUIPMENT GROUNDING CONDUCTORS. | | | | | | 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE LED | | | LIGHTING SHOWN FOR SIGN. THERE IS NO INFORMATION ON THE | | | DRIVER OR VOLTAGE WHICH DRIVES THESE LIGHTS. | | | NO DISCONNECT SWITCH SHOWN. | | | 600.7,600.6,600.5,250.122, ETC | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|