| Plan Review Notes For Permit 09030358 |
| Permit Number |
09030358 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-31 13:04:27 | ***DENIED*** | | | | | | 1) WORK SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION | | | CODE, 2007 EDITION. | | | | | | 2) WORK TO COMPLY WITH NFPA 72, 2002 EDITION. | | | | | | 3) THERE DOES NOT APPEAR TO BE ANY AUDIBLE/VISUAL | | | DEVICES IN THE PARKING GARAGE. PLEASE EXPLAIN WHAT | | | ALLOWS THIS ARRANGEMENT. | | | | | | 4) FIVE ANNUNCIATOR DEVICES ARE SHOWN ON THE PLANS, BUT | | | UNABLE TO LOCATE THE FIRE ALARM CONTROL PANEL. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|