2009-08-11 08:46:52BUILDING PLAN REVIEW
 PERMIT: 09030356
 ADD: 2730 S DIXIE HWY
 CONT: RUSSELL W CLARK, LLC
 TEL: (561)306-3634
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 11/2009
 1ST REVIEW
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME
 REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE
 2007 FBC BUILDING WITH 2009, 2007 EXISTING BUILDING
 CODEW/ 2009 SUPPLEMENTS. PLEASE INDICATE TO WHAT LEVEL
 OF ALTERATION IS TO TAKE PLACE OR HAS TAKEN PLACE UNDER
 THIS PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.2007
 EXISTING BUILDING CODE W/ 2009 SUPPLEMENETS
  
 3) 2ND REQUEST,THE FEE OF $500.00 IS LOW FOR THE SCOPE
 OF WORK LISTED ON THE PERMIT APPLICATION, THE
 EVALUATION IS MORE IN THE NEIGHBORHOOD OF $7,000.00.
 THE PRE-INSPECT INDICATED WORK HAS ALREADY STARTED,
 PLEASE INDICATE THE SCOPE OF WORK TO BE REVIEWED UNDER
 THIS PERMIT. DEPENDING ON THE SCOPE OF WORK THE DOLLAR
 AMOUNT LISTED ON THE PERMIT APPLICATION WILL CHANGE. W
 P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) 2ND REQUEST, PLEASE PROVIDE THE FOLLOWING
 INFORMATION TO DETERMINE THE MINIMUM BASE BUILDING
 REQUIREMENTS (TABLE 503/ 601. 110.2* W. P. B.
 ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503/
 CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .H ) NUMBER OF FLOORS/ OCCUPANCY SEPERATION?
 I ) SQ. FT. FOOTPRINT
  
 5) 2ND REQUEST, PLEASE PROVIDE A LIFE SAFET PLAN
 INDICATING EXIT ROUTES WITH TABLES AND CHAIRS.
 106.3.5(6).
  
 6) 2ND REQUEST, PROVIDE A PLAN WITH ACCESSIBLE SEATING.
 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS
 SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH
 THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18).
  
 7) 2ND REQUEST, PLANS FAIL TO IDENTY ANY FLOOR, WALL OR
 CEILING FINISHES, PLEASE PROVIDE IN COMPLIANCE WITH
 803.1 GENERAL. INTERIOR WALL AND CEILING FINISHES SHALL
 BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH
 INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE
 FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD
 AND SMOKE-DEVELOPED INDEXES.
  
 CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450.
  
 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450.
  
 CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450.
  
 EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN
 ACCORDANCE WITH SECTION 803.2.
  
 8) COMPLIED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved