| 2009-04-10 13:08:46 | * DENIED** |
| | |
| | 1) NOTE: RISER INDICATES THE METER CAN AT 200AMPS |
| | HOWEVER THIS IS NOT RATED FOR THE SERVICE SIZE AS |
| | SHOWN. |
| | 110.3 90.7 |
| | |
| | 2) NOTE: PLEASE SEE SMOKE ALARM WHICH NEEDS TO BE |
| | LOCATED INSIDE BEDROOM. THIS WOULD HAVE BEEN REDLINED |
| | IF IT WAS THE ONLY ITEM. NFPA-72 11.5.1. |
| | |
| | 3) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR THE WATER |
| | HEATER NEEDS TO BE SHOWN AT 125%. NEW IN 2005 NEC AS OF |
| | DECEMBER 2006. |
| | |
| | 4) NOTE: PLEASE SEE WATER HEATER IS SHOWN WITH A |
| | RECEPTACLE WITH CORD AND PLUG CONNECTION WHICH IS NOT |
| | PERMITTED. 422.30, 422.31 |
| | MUST BE A DISCONNECT. |
| | ** STORAGE TYPE WATER HEATER ALSO SHOWN AS BEING |
| | OUTSIDE WHICH MUST BE LISTED TO BE LOCATED OUTSIDE. |
| | |
| | 5) NOTE: MISSING REQUIRED DISCONNECT FOR CONDENSING |
| | UNIT. 440.11 |
| | |
| | 6) NOTE: MISSING WP GFI FOR CONDENSING UNIT PER 210.63, |
| | 210.8A |
| | |
| | 7) NOTE: PLEASE SEE PANEL SCHEDULE WHICH INDICATES A |
| | CIRCUIT FOR SMALL APPLIANCE #13 HOWEVER NO #13 IS ON |
| | PLANS. |
| | CIRCUIT #17 IS ALSO FEEDING MULTIPLE AREAS WHICH PER |
| | 210.11B1 IS REQUIRED TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. THE KITCHEN, DINING ROOM ETC ALSO |
| | FEEDS LIVING ROOM, LIGHTS ETC./ |
| | PLEASE SEE 210.52B1, 210.11C1, AND 220.53 FOR THE LOADS |
| | WHICH ARE REQUIRED TO BE FIGURED. |
| | |
| | 8) NOTE: ALL AIC RATINGS MUST BE STATED ON PLANS. |
| | PLEASE KEEP IN MIND MANY OF THE FPL TRANSFORMERS ARE |
| | BEING UPDATED WHICH MAY HAVE A HIGHER AVAILABLE FAULT |
| | CURRENT. PLEASE BE SURE TO CHECK WITH THE LOCAL FPL |
| | REPRESENTATIVE. |
| | |
| | 9) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL |
| | SCHEDULE FOR MAIN HOUSE IS LISTED AS 150AMP MCB YET |
| | RISER SHOWS COMPLETELY DIFFERENT EQUIPMENT. |
| | 230.70, 230.71, 110.3 SECTIONS GIVEN AS GENERAL |
| | SECTIONS DUE TO MORE COORDINATION OF PLANS. |
| | FBC 106.1.1 FOR CLARITY. |
| | |
| | 10) NOTE: PLEASE PROVIDE A RESPONSE FOR SCOPE OF WORK |
| | AT GUEST HOUSE/ COTTAGE. WILL THE NEW ELECTRICAL |
| | SERVICE BE THE ONLY WORK? |
| | |
| | 11) NOTE: PLANS DO NOT INDICATE LOAD CALCULATIONS FOR |
| | SERVICE. PLEASE SEE NEC 220 |
| | ONLY SHOWS LOAD FOR MAIN HOUSE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |