| Plan Review Notes For Permit 09030333 |
| Permit Number |
09030333 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-29 16:33:06 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | FROM FIRST REVIEW, NOT ADDRESSED: | | | | | | 1. PLEASE REVISE GOVERNING CODE. | | | | | | 2. PLANS STATE THAT THIS SIGN WILL BE INSTALLED ON THE | | | FASCIA. ELEVATION SHOWS THIS INTO BUILDING FACE,SPECIFY | | | MASONRY ANCHORS. PLEASE CLARIFY FBC1609. SPEC SHEETS | | | FOR ANCHORS AND CALCULATIONS MAY BE REQUIRED. | | | | | | 3. SPECIFICATION FOR ATTACHMENT IS FOR A RECTANGULAR | | | SIGN, THIS SIGN IS OVAL. PLEASE REVISE SPECIFICATION TO | | | BE CLEAR AS TO NUMBER OF ANCHORS REQUIRED TO RESIST | | | WIND LOADS FBC 1609. | | | | | | 2ND REVIEW CLARIFICATION; PLEASE SPECIFY NUMBER OF | | | TAPCONS PROPOSED. THE SPEC STATES "TOP" AND "BOTTOM", | | | WHERE DO THE "TOP" AND "BOTTOM" START AND END ON AN | | | OVAL SIGN? |
|