2009-05-06 12:19:37 
 BUILDING PLAN REVIEW
 PERMIT:09030299
 ADD: 6921 ISLA VISTA DR
 CONT: EMERGENCY POWER SYSTEMS INC.
 TEL: (561)723-5523
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 BUILDING:
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDINGCODE, RESIDENTIAL WITH 2009 SUPPLEMENTS.
  
  
 2) MISSING WIND DESIGN:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLEASE PROVIDE MANUFACTUREERS INFORMATION ON THE
 PRECAST FACTORY (CONCAST) PAD, IT MAY BE APPROVED BY
 PALM BCH CTY, BUT THIS IS JOB LOCATION IS NOT WITHIN
 PALM BEACH COUNTY UNINCORPORATED JURISDICTION. SHOW
 PRODUCT APPROVAL FOR USE IN THIS WIND ZONE. R401.2
 REQUIREMENTS FOUNDATIONS SHALL BE ABLE TO RESISST ALL
 LOADS FROM UPLIFT AND OVERTURNING.
 R402.3 PRECAST CONCRETE. APPROVED PRECAST CONCRETE
 FOUNDATIONS SHALL BE DESIGNED AND INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE AND THE
 MANUFACTURERS INSTALLATION INSTRUCTIONS, PLEASE
 PROVIDE.
  
  
 MECHANICAL:
  
 1) PLEASE INDICATE ON EITHER A SURVEY OR SITE PLAN THE
 LOCATION OFTHE GENERATOR, THE DISTANCE FROM PROPERTY
 LINES AND FROM BUILDINGS, PLEASE ALSO INDICATE ON THE
 SITE PLAN ANY DOORS OR WINDOWS AND THE DISTANCE AWAY
 FROM THE GENERATOR. PROVIDE PLANS ENOUGH TO VERIFY
 LOCATION OF GENERATOR VERSES BUILDING OPENINGS WINDOWS,
 DOORS OR SOFFIT TYPE VENTS, ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL
 TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
  
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
  
 3. THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET INTO THE BUILDING.
  
 4. THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO WALLS PERPENDICULAR TO EACH OTHER.
  
 5. THE VENT TERMINATION SHALL NOT BE MOUNTED DIRECTLY
 ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY FROM AN
 OIL TANK VENT OR GAS METER.
  
 6. THE BOTTOM OF THE VENT TERMINATION SHALL BE LOCATED
 AT LEAST 12 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1. WHERE LOCATED ADJACENT TO WALKWAYS, THE TERMINATION
 OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
  
 2. VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) ABOVE
 ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 MM).
  
 3. WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM SUCH STRUCTURE.
  
 4. THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 MM)
 BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 FOR THE BUILDING.
  
 5. A VENT CAP SHALL BE INSTALLED TO PREVENT RAIN FROM
 ENTERING THE VENT SYSTEM.
  
 6. THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
 THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL BE DISCHARGED OUTDOORS AT A POINT WHERE IT WILL
 NOT CAUSE A NUISANCE AND FROM WHICH IT CANNOT AGAIN BE
 READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC OR CRAWL SPACE
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved