| | APPLICATION #09030254 ELECTRICAL PLAN REVIEW |
| | 310 CORDOVA ROAD 10/27/09 |
| | WEST PALM BEACH, FL. |
| | |
| | REVISION DENIED |
| | |
| | 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). |
| | CORRELATE WITH MECHANICAL PLAN, SHEET M1. NOTE THE NEW |
| | AIR HANDLER LOCATION ON SHEET M1 OF THIS PLAN DOES NOT |
| | CORRELATE TO THE LOCATION OF THE PERMIT SET SHEET E1 |
| | |
| | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | THE LOCATION MUST BE ON THE REVISION. THE PERMIT SET OF |
| | PLANS INDICATES PANELS "M" & "H" PANEL SCHEDULES BUT |
| | ONLY ONE PANEL SHOWN ON THE FLOOR PLAN IN THE MAIN |
| | HOUSE. NOTE: THE REVISION SUBMITTED ON SEPTEMBER 3RD |
| | DID NOT HAVE THE PANELS LABELED ON THE RISER SHEET E3 |
| | |
| | 3} SUBMIT REVISED SHEET E3 WITH REVISED LOAD |
| | CALCULATIONS AND PANEL SCHEDULES TO SHOW ADDED (OR |
| | EXISTING) LOADS, WALL HEATERS, TANKLESS WATER |
| | HEATERS(NOT SHOWN ON REVISED PLUMBING PLAN) TREADMILL, |
| | SPACE HEATER WINDOW A/C (DEDICATED) CIRCUITS, ETC. |
| | |
| | 4} THE PANEL LOCATION IN THE APARTMENT ON SHEET E1 IS |
| | EITHER IN VIOLATION OF 240.24(E) BATHROOMS OR 110.26 IF |
| | FACING STUDIO 1, DEPENDING ON WHAT THE SHADED AREA IN |
| | THE STUDIO REPRESENTS, LABEL SAME FOR CLARIFICATION. |
| | |
| | 5} KITCHEN RECEPTACLE MUST COMPLY WITH 210.8(A)(6) GFI, |
| | ALL UNITS. THE ONLY ONES LABLED ARE IN THE MAIN HOUSE @ |
| | THE SINK. LABEL ALL. |
| | |
| | 6} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). SEE BATH #3 SHEET E2 |
| | APARTMENT. |
| | |
| | 7} 210.8(A)(3) DWELLING UNITS ALL 125-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED |
| | IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL |
| | HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL OUTDOORS.*** LABEL ALL, SEE E1 1ST FLOOR |
| | PLAN. |
| | |
| | 8} THE LOCATION OF THE TANKLESS WATER HEATER LOCATED IN |
| | THE STORAGE ROOM, SHEET E1, IS IN VIOLATION OF 110.26 |
| | SPACING REQUIREMENTS IF LOCATED WHERE THE |
| | ???RECEPTACLE??? IS SHOWN. SEE 240.24(D) IF AN |
| | OVERCURRENT DEVICE IS TO BE INSTALLED IN THE STORAGE |
| | ROOM. |
| | |
| | NOTE: THE #6 GROUND SHOWN INSTALLED WITH THE |
| | SERVICE-ENTRANCE CONDUCTORS, SHEET E3, MUST NOT BE |
| | INSTALLED AND IS A VIOLATION OF 250.6 AND SHALL BE |
| | INSTALLED PER 250.24(A) & (A)(1). |
| | |
| | PLEASE RESPOND TO REVIEW COMMENTS IN WRITING |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |