| | APPLICATION #09030225 ELECTRICAL PLAN REVIEW |
| | 310 CORDOVA ROAD 3/27/09 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE AN AIC RATING, AND |
| | LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 2} THERE DISCONNECTS ON THE RISER DIAGRAM LABELED 1ST |
| | AND 2ND FLOOR APARTMENTS, BUT NO PANEL SHOWN ON THE 2ND |
| | FLOOR PLAN, SHEET E2. LOCATE SAME OR INDICATE IF |
| | REMOVED. 215.5 |
| | |
| | 3} PROVIDE A LOAD CALCULATION AND PANEL SCHEDULES FOR |
| | THE ENTIRE SERVICE, INCLUDING THE APARTMENTS. 215.5, |
| | 408.4. |
| | |
| | 4} THE PANEL LOCATION IN THE APARTMENT ON SHEET E1 IS |
| | EITHER IN VIOLATION OF 240.24(E) BATHROOMS OR 110.26 IF |
| | FACING STUDIO 1. |
| | |
| | 5} THE MAIN HOUSE PANEL LOCATED BEHIND THE STACK |
| | WASHER/DRYER IS IN VIOLATION OF 110.26 AND 240.24(D) IF |
| | THIS IS TO BE STORAGE ROOM. |
| | |
| | 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN, ALL |
| | UNITS. |
| | |
| | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR EXAMPLES |
| | OF DEFICIENCIES. |
| | |
| | 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. |
| | |
| | 9} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO |
| | OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. |
| | |
| | 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |