| 2009-04-22 16:03:27 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT |
| | PICK UP. |
| | |
| | 3- OWES $4.84 FOR RADON FEES. CHAPTER 10D-91, FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 4- CURRENT CODE IN EFFECT IS THE 2007 FLORIDA |
| | RESIDENTIAL CODE, NOT THE 2004. NEED TO REVISE DESIGN |
| | CRITERIA AND EVERY RELEVANT NOTE ON SHEET S3 TO THE |
| | 2007 CODES. |
| | ***NOTE: SEE SEC. R301.1 OF 2007 FLORIDA RESIDENTIAL |
| | CODE AND SEC. 1609.1.1 FBC 2007 TO DETERMINE WHICH |
| | DESIGN CRITERIA IS GOING TO BE USED. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) NEW SKYLIGHT AS SHOWN ON PLANS. NONE PROVIDED AT |
| | THIS TIME. |
| | |
| | B) GARAGE DOORS. FLORIDA PRODUCT APPROVAL FL6218-R8 |
| | SUBMITTED IS FOR CODE VERSION 2004. NEED TO PROVIDE |
| | CURRENT 2007 CODE VERSION. |
| | |
| | C) FLAT ROOF. (1) FLORIDA PRODUCT APPROVAL FL735-R2 |
| | SUBMITTED IS FOR 2004 CODE VERSION. NEED CURRENT 2007 |
| | CODE VERSION. (2) NOA-06-0601.05 SUBMITTED IS FOR |
| | CEMENTIOUS WOOD FIBER DECKS. PLANS SUBMITTED SPECIFY |
| | PLYWOOD ROOF SHEATHING. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR PROPER ROOF SHEATHING TYPE. (3) CLEARLY |
| | IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. |
| | (4) IF APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7, THEN NEED TO PROVIDE SIGNED AND SEALED |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. (***NOTE: IF SELECTED ASSEMBLY IS LIMITED BY |
| | GENERAL LIMITATION #9, THEN IT CAN'T BE USED BECAUSE |
| | THIS LIMITATION DOESN'T ALLOW NAIL ENHANCING. SEE |
| | GENERAL LIMITATION #9). (5) PROVIDE CURRENT PRODUCT |
| | APPROVAL FOR INSULATION. FLORIDA PRODUCT APPROVAL |
| | FL4205-R2 SUBMITTED IS FOR 2004 CODE VERSION. NEED TO |
| | PROVIDE CURRENT 2007 CODE VERSION. |
| | |
| | D) INSWING DOOR AS SHOWN ON PLANS. PRODUCT APPROVAL |
| | SUBMITTED IS FOR OUTSWING DOORS ONLY. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL NEW OR RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-101.2.2 FBC 2007. |
| | NOTE: PLEASE MAKE SURE ALL INFORMATION IS COMPLETE AND |
| | SIGNED AND DATED BY THE PREPARER AND BY OWNER/AGENT. |
| | |
| | 8- REVISE DETAIL C/A6. WINDOW BUCK NEED TO PROVIDE FULL |
| | SUPPORT TO THE WINDOW/DOOR FRAME AS REQUIRED BY SEC. |
| | R613.6.1.1 OF 2007 FLORIDA RESIDENTIAL CODE. BEVELED |
| | BUCKS DON'T PROVIDE FULL SUPPORT. REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |