Plan Review Notes
Plan Review Notes For Permit 09030236
Permit Number 09030236
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-02 15:24:52** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT A MINIMUM OF TWO SETS OF PLANS
 FOR REVIEW, PROCESSING AND PERMITTING.
 FBC 106.1
  
 2) NOTE: PLEASE KNOW THE ONE SET SUBMITTED IS ALL
 COLORED PHOTO-COPIES OF ORIGINAL SIGNED AND SEALED
 PLANS WHICH IS NOT PERMITTED.
 FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE BE SURE ELECTRICAL PLANS/SHEETS CONTAIN
 MORE ELECTRICAL INFORMATION ON GROUNDING PER 600.7,
 250, BRANCH CIRCUIT LOADS AND DETAILS PER 600.5, 240.4,
 220 ETC
 AS THERE IS NOT ENOUGH INFORMATION FOR REVIEW SOME
 COMMENTS CAN NOT BE MADE AT THIS TIME.
  
 4) NOTE: THE CODES REFLECTED ON PLANS ARE NOT CORRECT.
 PER FS 553.73 THE STATE OF FLORIDA HAS ADOPTED THE 2007
 FBC WITH OTHER ADOPTED COEDS.
 PLEASE REVISE PLANS AND BE SURE TO LIST THE CORRECT
 NEC. ( 2005).
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  