| 2009-03-26 08:43:31 | | | | | | | APPLICATION #09030201 ELECTRICAL PLAN REVIEW | | | 5514 WESTERN AVENUE 3/25/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 3} CIRCUIT NUMBER 6,8 FOR THE AHU OCP IS INADEQUATE PER | | | 424.3(B), NEC (125%). | | | | | | 4} PER 210.8(A) (6) GFI PROTECTION IS REQUIRED IN | | | KITCHENS ??? WHERE THE RECEPTACLES ARE INSTALLED TO | | | SERVE THE COUNTERTOP SURFACES, THIS INCLUDES THE | | | COUNTERTOP SURFACES AT THE RANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|