 APPLICATION #09030201 ELECTRICAL PLAN REVIEW
 5514 WESTERN AVENUE 3/25/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} CIRCUIT NUMBER 6,8 FOR THE AHU OCP IS INADEQUATE PER
 424.3(B), NEC (125%).
  
 4} PER 210.8(A) (6) GFI PROTECTION IS REQUIRED IN
 KITCHENS ??? WHERE THE RECEPTACLES ARE INSTALLED TO
 SERVE THE COUNTERTOP SURFACES, THIS INCLUDES THE
 COUNTERTOP SURFACES AT THE RANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  