2009-04-15 10:19:47RESIDENTIAL (R3) NEW SINGLE FAMILY RESIDENCE, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- SHEET 3:
 A) REVISE ROOF SHEATHING SPECIFICATIONS. NEED TO REVISE
 TYPE OF NAIL AND NAIL SPACING. NEED MIN. 8D RING SHANK
 NAILS AND NAIL SPACING TO BE MIN. 4"O.C. FOR ZONE 3.
 SEE SEC. R803.2.3.1 AND FIGURE R803.2.3.1 OF 2007
 FLORIDA RESIDENTIAL CODE. NOTE THAT GABLE ENDS ARE ZONE
 3 FOR THE FIRST 5'. REVISE AND IDENTIFY ROOF ZONES AS
 REQUIRED.
  
 B) GABLE END DETAIL NEEDS TO COMPLY WITH THE
 REQUIREMENTS OF SECTIONS R609.4 THRU R609.4.4 OF 2007
 FLORIDA RESIDENTIAL CODE. SEE REFERENCED FIGURES AND
 REVISE AS REQUIRED.
  
 C) SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON GABLE
 END DETAIL AS REQUIRED BY SEC. R602.1.2 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 D) SPECIFY 2 LAYERS OF VAPOR BARRIER WHEN APPLYING
 STUCCO AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE NOTE #2 AS REQUIRED.
  
 2- SHEET 4:
  
 A) PROVIDE MANUFACTURER CUT SHEETS FOR WINDOW #4 IN
 MASTER BEDROOM TO VERIFY COMPLIANCE WITH MIN. SIZE
 REQUIRED BY SEC. R310 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE SIZE OF DOOR BUCK AS REQUIRED TO COMPLY WITH
 SEC. R613.6. SIZE OF BUCK NEED TO PROVIDE FULL SUPPORT
 TO THE DOOR FRAME. SEE SIZE OF DOOR FRAME ON PRODUCT
 APPROVAL AND REVISE AS REQUIRED.
  
 C) DESIGN PARAMETERS: SPECIFY ALL LOADS AS REQUIRED BY
 SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE. NEED TO SPECIFY THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5.
  
 D) UPDATE THE CODE EDITION SPECIFIED ON WIND LOADS.
 NEED TO SPECIFY 2007 FLORIDA RESIDENTIAL CODE, NOT
 2004.
  
 E) COMPONENTS AND CLADDING WIND PRESSURES SHOWN ON WIND
 LOADS DON'T MATCH COMPONENTS AND CLADDING WIND
 PRESSURES SPECIFIED ON DOOR AND WINDOW SCHEDULE. REVISE
 AS REQUIRED.
  
 F) SPECIFY SAFETY GLASS ON FOR WINDOW #5 ON MASTER
 BATHROOM AS REQUIRED BY SEC. R308.4 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 3- SURVEY TO HAVE ORIGINAL SIGNATURE (NOT RUBBER STAMP)
 AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL SITE PREPARATION, LABOR
 AND MATERIALS, PROFESSIONAL FEES AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC. OWES $3066.98 FOR UPDATED
 VALUATION AND RADON FEES.
  
 5- CLARIFY TYPE OF WINDOW TO BE USED IN MASTER
 BATHROOM. WINDOW SCHEDULE CALLS FOR SINGLE HUNG WINDOW,
 WHILE EXTERIOR ELEVATION SHOWS FIXED WINDOW. REVISE AS
 REQUIRED. IF USING FIXED WINDOW, THEN PROVIDE
 CORRESPONDING PRODUCT APPROVAL.
  
 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. PRODUCT APPROVAL FL10674-R1 SUBMITTED
 IS MISSING THE DRAWINGS THAT WERE SUBMITTED TO GET THE
 PRODUCT APPROVAL.
  
 B) SINGLE HUNG/DOUBLE HUNG WINDOWS. PRODUCT APPROVAL
 FL5043 SUBMITTED IS FOR 2004 CODE VERSION. CURRENT CODE
 IN EFFECT IS THE 2007 CODE VERSION.
 ALSO, PROVIDE DRAWINGS THAT WERE SUBMITTED FOR APPROVAL
 ALONG WITH THE TECHNICAL INFORMATION SHOWING THE DESIGN
 PRESSURES FOR SELECTED WINDOWS TO VERIFY COMPLIANCE
 WITH ENGINEER'S CALCULATED DESIGN PRESSURES.
  
 C) EXTERIOR SWING DOORS. PRODUCT APPROVAL FL7551
 SUBMITTED IS FOR 2004 CODE VERSION. NEED 2007 CODE
 VERSION.
 ALSO, PROVIDE INFORMATION SHOWING THE DESIGN PRESSURES
 FOR SELECTED DOORS.
  
 D) SLIDING GLASS DOORS. PRODUCT APPROVAL FL1824-R0
 SUBMITTED IS FOR 2001 CODE VERSION. NEED TO PROVIDE
 2007 CODE VERSION.
 ALSO, PROVIDE DRAWINGS SHOWING THE DESIGN PRESSURES FOR
 SELECTED DOORS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SELECTED ANCHOR. THIS
 APPLIES TO STRUCTURAL CONNECTORS ONLY. COMPLETE PRODUCT
 APPROVAL REPORT IS REQUIRED FOR ALL OTHER PRODUCT
 APPROVALS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 8- ENERGY CALCULATIONS:
 A) PAGE 1 OF 5 STATES THAT THIS IS NOT A WORST CASE
 SCENARIO. ORIENTATION OF WINDOWS SHOWN ON PAGE 3 OF 5
 DOESN'T MATCH ORIENTATION OF BUILDING. SEE SURVEY AND
 REVISE AS REQUIRED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME AND PERMIT OFFICE.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) PROVIDE INFORMATION FOR WINDOWS SHOWING COMPLIANCE
 WITH THE U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7.
 NOTE: THIS IS REQUIRED WHEN CALCULATIONS ARE DONE USING
 SPECIFIC FACTORS AND NOT THE DEFAULT FACTOR OF THE
 PROGRAM USED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  