| Plan Review Notes For Permit 09030187 |
| Permit Number |
09030187 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-11 11:16:55 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. WITH 2008 | | | REVISIONS. | | | | | | 1- FLORIDA PRODUCT APPROVAL FL6465 SUBMITTED IS FOR | | | 2004 CODE VERSION. AS OF MARCH 1ST 2009 THE CODE IN | | | EFFECT IS THE 2007 FBC. NEED TO PROVIDE PRODUCT | | | APPROVAL FOR 2007 CODE VERSION. | | | | | | 2- REVISE INSTALLATION SCHEDULE SUBMITTED: | | | A) SPECIFY THE DESIGN PRESSURES AS REQUESTED ON COLUMN | | | #3. PROVIDE ACTUAL DESIGN PRESSURES CALCULATIONS OR USE | | | TABLE R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE. SEE | | | ATTACHED COPY. | | | | | | B) SPECIFY SHUTTER MOUNTING CONDITION ON COLUMN #4. | | | THIS APPLIES TO THE PROPOSED INSTALLATION. EG: WALL | | | MOUNT, BUILT OUT, ETC. EG: SEE SHEET 5 OR 10 OF | | | ACCORDION DRAWINGS SUBMITTED AND CIRCLE SPECIFIC | | | MOUNTING CONDITIONS. INFORMATION SUBMITTED SPECIFIES | | | THE ANCHOR TYPE TO BE USED. THIS IS TO BE SPECIFIED ON | | | COLUMN 10 OF THE INSTALLATION SCHEDULE. SEE COMMENTS ON | | | INFORMATION SUBMITTED. | | | | | | C) REVISE COLUMN #6. SHUTTER SPAN IS FOR THE LENGTH OF | | | THE ACCORDION BLADES, NOT FOR THE WIDTH OF THE OPENING. | | | REVISE AS REQUIRED. | | | ***NOTE: COORDINATE SHUTTER SPAN WITH THE EDGE DISTANCE | | | ON COLUMN #8. ALSO, TAKE INTO CONSIDERATION THAT THE | | | EDGE DISTANCE EXCLUDES THE STUCCO THICKNESS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|