2009-03-18 14:40:49RESIDENTIAL (R3) SOLAR PANELS, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008
 REVISIONS.
  
 1- AS OF MARCH 1ST 2009 THE CODE IN EFFECT IS THE 2007
 FBC WITH THE 2008 REVISIONS. ENGINEER'S WIND LOAD
 DESIGN CRITERIA ON SHEET 3 OF 3 SUBMITTED THE FIRST
 TIME SPECIFIED THE ASCE 7-05 AS THE REFERENCE FOR THE
 DESIGN. THIS IS THE CORRECT ASCE 7 EDITION TO BE USED
 UNDER THE 2007 FBC. CALCULATIONS SUBMITTED NOW ARE DONE
 BASED ON THE ASCE 7-02. NEED TO REVISE CALCULATIONS
 USING THE ASCE 7-05 EDITION.
  
 2- CALCULATIONS SUBMITTED ARE USING "TOWN OF PALM
 BEACH" TABLE FOR WALL COMPONENTS AND CLADDING. THIS
 TABLE IS NOT ADOPTED BY THE CITY OF WEST PALM BEACH.
 THEREFORE IT CAN'T BE USED. ON THE OTHER HAND, DESIGN
 CRITERIA SHALL BE DONE USING THE ASCE 7-05 TABLES
 WITHOUT MIXING AND MATCHING OTHER TABLES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712