| Plan Review Notes For Permit 09030178 |
| Permit Number |
09030178 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-16 15:46:04 | RESIDENTIAL (R3) SOLAR PANELS, BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008 | | | REVISIONS. | | | | | | 1- SHEET 3 OF 3 OF ENGINEERED DRAWINGS: | | | A) SPECIFY POST SUPPORT SIZE, MATERIAL. | | | | | | B) CLARIFY HOW IS POST SUPPORT ATTACHED TO THE ROOF. | | | DETAILS 5/3 AND 6/3 SHOW 6 -1/4" LAG SCREWS. ACCORDING | | | TO THESE DETAILS THE SCREWS ARE ATTACHED TO THE PLYWOOD | | | SHEATHING AND NOT TO THE FRAMING MEMBER. PROVIDE | | | ENGINEERING ANALYSIS TO SHOW HOW THE PLYWOOD IS GOING | | | TO RESIST THE WIND LOADS. SEC. R301 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | ALSO, SPECIFY HOW LONG ARE THE SCREWS. | | | | | | C) SPECIFY HOW MANY 3/8" SS BOLTS ARE REQUIRED AT EACH | | | CONNECTION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|