| 2009-05-08 14:36:20 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | COMMENTS FROM FIRST REVIEW NOT ADDRESSED: |
| | |
| | 1. (PREVIOUSLY #6, FIRST REVIEW) THE APPLICATION DOES |
| | NOT GIVE CLEAR DESCRIPTOIN OF THE INTENDED WORK OF THE |
| | AREA. BOTH THE APPLICATION AND THE DRAWINGS SHALL |
| | CLEARLY SHOW IN DETAIL THE LOCATION AND AREA OF THE |
| | PROPOSED CHANGES. PROVIDE A WALL LEGEND CLEARLY |
| | INDICATING THE NEW WALLS AND EXISTING WALL WITH |
| | DESCRIPTION OF ALL MATERIALS. THE DRAWINGS SHALL ALSO |
| | STATE THE USE OF EACH ROOM OF THE SPACE. |
| | |
| | 2ND REVIEW, NO WALL LEGEND PROVIDED. SOME WALLS ARE |
| | SHOWN IN GREY, SOME IN BLACK, AND SOME ARE DOUBLE |
| | BLACKLINE. WHICH ARE NEW, EXISTING? SCOPE IS NOT CLEAR; |
| | PLEASE PROVIDE WALL LEGEND. |
| | |
| | 2. THE NEW CLOSET DOOR (DOOR 2) INTERFERES WITH THE |
| | DOOR SWING OF THE BATHROOM DOOR FBC1005, AND THE |
| | PROPOSED NEW (CLOSET) WALL OBSTRUCTS THE REQUIRED |
| | MANEUVERING CLEARANCE, PULL SIDE, FBC11 FIGURE 25. IT |
| | APPEARS THAT REVERSING THE BATHROOM DOOR MAY RESOLVE |
| | THE ISSUE, BUT ANY CODE COMPLIANT OPTION IS ACCEPTABLE. |
| | |
| | 3. THE RAMP HANDRAILS LACK THE REQUIRED EXTENSION, |
| | FBC11-4.8.5(2). |
| | |
| | 4. FBC11-4.28.2, VISUAL ALARM REQUIRED IN BATHROOM. |
| | (NEW COMMENT, CAN BE PROVISO/REDLINE.) |
| | |
| | 5. PLEASE NOTE THAT IT IS POSSIBLE THAT THIS REVIEW CAN |
| | BE PASSED WITH PROVISO/REDLINE (REVISION REQUIRED), |
| | PLEASE CONTACT ME IF THIS APPLICATION PASSES ALL OTHER |
| | TRADES. |
| | |
| | 6. PLEASE PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. |
| | FBC*106. |