| 2009-03-13 16:27:07 | BUILDING PLAN REVIEW |
| | PERMIT: 09030109 |
| | ADD: 1804 N. DIXIE HWY UNIT C |
| | CONT: HOLEMAN HOMES INC. |
| | TEL: (561)743-0687 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH THE 2009 SUPPLEMENTS. THE DESIGN UNDER |
| | WHICH THE PROJECT IS BASE SHALL BE STATED ON THE PLANS. |
| | |
| | 4) 2007 FBC (EXISTING) 401.4 A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF |
| | THIS CODE. THIS INFORMATION SHALL BE INDICATED ON THE |
| | PLANS. |
| | |
| | 5) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION |
| | PER CHAPTER 6 AND TABLE 503, THE USE AND OCCUPANCY PER |
| | CHAPTER 3. THIS INFORMATION IS REQUIRED SO THAT ANY |
| | ADDITIONAL CONSTRUCTION IN ACCORDANCE WITH THE ORIGINAL |
| | BUILDING TYPE. |
| | |
| | 6) THE APPLICATION DOES NOT GIVE CLEAR DESCRIPTION OF |
| | THE INTENDED WORK OF THE AREA. BOTH THE APPLICATION AND |
| | THE DRAWINGS SHALL CLEARLY SHOW IN DETAIL THE LOCATION |
| | AND AREA OF THE PROPOSED CHANGES. PROVIDE A WALL LEGEND |
| | CLEARLY INDICATING THE NEW WALLS AND THE EXISTING WALL |
| | WITH A DESCRIPTION OF ALL MATERIALS. THE DRAWINGS SHALL |
| | ALSO STATE THE USE OF EACH ROOM OF THE SPACE. THE PLANS |
| | SHOW A SECTION OF A MEZZANINE, PLEASE INDICATE CLEARLY |
| | THE LOCATION OF THE MEZZANINE ON THE DRAWINGS. THE |
| | DOCUMENTS SHALL CLEARLY SHOW THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED FBC 106.1.1 |
| | |
| | 7) SHEET 1.0A SHOWS A SECTION FOR A RAISED PLATFORM ON |
| | 2 X 8 WITH ?? INCH PLYWOOD. THE PLATFORM SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH FBC 2007 410.3 AND |
| | 410.4. INDICATE THE USE OF THE PLATFORM ON THE |
| | DRAWINGS. SHOW THE ACCESSIBILITY ENTRANCE TO THE |
| | PLATFORM FBC 11-4.1.2 VERTICAL ACCESSIBILITY, SHALL BE |
| | PROVIDED TO ALL LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. SHOW COMPLIANCE. HANDRAILS MAY BE REQUIRED |
| | WHEN ADDITIONAL INFORMATION SHOWN WITH THE HEIGHT AND |
| | USE OF THE PLATFORM. |
| | |
| | 8) THERE ARE SOME SYMBOLS ON THE PLANS WITH NUMBERS |
| | INSIDE, IF THESE SYMBOLS ARE MAKING REFERENCE TO |
| | DETAILS PROVIDE THE DETAIL DRAWINGS. |
| | |
| | 9) PROVIDE THE CONNECTION DETAIL OF THE 2 X 8 TO THE |
| | EXISTING FLOOR AND EXISTING WALLS WITH THE TYPES OF |
| | CONNECTION STRAPS; AND THE NAIL PATTERN FOR THE |
| | PLYWOOD. STATE THE TYPE OF WOOD TO BE USED AND THE TYPE |
| | OF EXISTING FLOOR. THE UNIFORM DISTRIBUTED LIVE LOAD |
| | SHALL BE GIVEN PER TABLE 1067.1, ALONG WITH THE LATERAL |
| | SUPPORT PER 2308.8.5 AND THE GRADE/ SPECIES AND NUMBER |
| | FOR THE TYPE OF WOOD USED FBC 2304.7.1. |
| | |
| | NOTE: ADDITIONAL NOTES MAY APPEAR ON SECOND REVIEW |
| | DEPENDING ON THE RESPONSE TO THE ABOVE NOTES. |
| | |