| 2009-04-06 11:10:03 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | PLEASE SEE COMMENT FROM REVIEW OF MASTER PERMIT; |
| | 09010024, AND PREVIOUS ROOF PERMIT REVIEW : |
| | |
| | |
| | 1. CONTRACTOR MUST SELECT AN APPROVED ASSEMBLY AND |
| | SPECIFY ENHANCED FASTENING. |
| | |
| | A DIFFERENT NOA WAS SUBMITTED, ASSEMBLY SELECTED WHICH |
| | MEETS A MAXIMUM DESIGN PRESSURE OF -52.5PSF. ENGINEER'S |
| | REQUIREMENT FOR ZONES 2 AND 3 IS -79.2PSF. PLEASE |
| | ADDRESS THE FOLLOWING: |
| | |
| | A. CLARIFY WHY ZONE 3 IS LOW; SEE FBC TABLE 1609.6.2.1 |
| | (-89PSF REQUIRED FOR ZONE 3). CONTRACTOR MAY REMOVE THE |
| | ENGINEERING AND USE FBC TABLE 1609.6.2.1 FOR DESIGN |
| | PRESSURES FOR THE ROOF, OR ENGINEER CAN CLARIFY TO USE |
| | -79PSF (PROVIDE CALCULATIONS). |
| | |
| | B. SPECIFY ENHANCED FASTENING FOR CORNER AND PERIMETER |
| | ZONES. |
| | |
| | 2. A NEW NOA SUBMITTED; PLEASE HAVE THIS REVIEWED BY |
| | DESIGNER OF RECORD FBC*106.3.3. |
| | |
| | 3. AS THIS IS A CHANGE TO THE MASTER PERMIT, THIS WILL |
| | BE SUBMITTED AS A REVISION TO THE MASTER. INFORMATIONAL |
| | ONLY. |
| | |
| | |
| | |