2009-04-06 14:03:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE GOVERNING CODE TO REFLECT CURRENT
 CODE, INCLUDING 2008 SUPPLEMENTS.
  
 2. PLEASE HAVE ENGINEER EXPLAIN RATIONALE FOR EXPOSURE
 B. IT APPEARS THAT THIS IS IN EXPOSURE C.
  
 3. PLEASE CLARIFY THE STATEMENT ON THE PLAN WHICH
 STATES THAT WEST OF THE TURNPIKE IS 130MPH. ALL OF THE
 CITY OF WEST PALM BEACH IS LOCATED IN THE 140MPH WIND
 ZONE, FBC R301.
  
 4. THERE ARE REFERENCES TO PALM BEACH COUNTY
 REQUIREMENTS AND BUILDING FORMS. THIS JOB IS LOCATED IN
 THE JURISDICTION OF THE CITY OF WEST PALM BEACH.
  
 5. PROVIDE EVIDENCE OF THE "EXISTING SHUTTERS," SUCH AS
 A PERMIT NUMBER. I WAS UNABLE TO LOCATE A PERMIT FOR
 THIS WORK. FBC R301.2.1.
  
 6. PROVIDE THE PRODUCT APPROVAL FOR THE DOOR, FAC9B72.
  
 7. A SET OF PLANS HAS BEEN RETAINED. WHEN RESUBMITTING,
 PLEASE SUBMIT TWO COMPLETE SETS OF PERMIT DOCUMENTS.
 NOTE THAT ONLY ONE SET OF PRODUCT APPROVALS WAS
 SUBMITTED; TWO REQUIRED.
  
  
  
  
  
  
  
  
  