2009-04-13 11:42:02** DENIED**
  
 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF
 PLANS BOUND TOGETHER.
 PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM CODES ARE
 STATED ON PLANS.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: LIGHTING CONTROLS PER 13-415.1.AB.1.1,.1.2
 REQUIRED.
  
 3) NOTE: PRESCRIPTIVE LIGHTING PERFORMANCE NEEDS TO BE
 SHOWN PER 13-415.AB.5. THIS IS ONLY FOR NEW BEING
 INSTALLED.
 THE PLANS DO NOT INDICATE SPECIFIC LIGHTING.
  
 4) NOTE: PLEASE COMPLETE CIRCUITING TO NEW RECEPTACLES
 AND LIGHTING. PLEASE INDICATE WHERE THEY ARE BEING FED
 FROM. WHAT SIZE CIRCUIT, OVER CURRENT PROTECTION ETC.
 408.4, 240.4, 310.16
  
 5) NOTE: ADDRESS ON PLANS STATES * OLD OKEECHOBEE RD*
 ACTUAL LOCATION IS JUST * OKEECHOBEE RD*. THIS OFFICE
 IS AWARE THAT STREET SIGNS ETC MAY STATE * OLD* HOWEVER
 ACTUAL LEGAL ADDRESS DOES NOT INCLUDE THIS WORDING.
 PLEASE ADJUST PLANS.
 FAC61G1-16.004
 FBC 106.5
  
 6) NOTE: PLEASE SEE NFPA-101 7.8.1.3, 7.9.1 FOR
 REQUIRED LIGHTING LEVELS ON STAIRS WHICH REQUIRE 10FT
 CANDLES UNDER NORMAL AND IS PERMITTED DOWN TO 1FT
 CANDLE UNDER EMERGENCY. PLEASE ALSO SEE 700.12F AND
 700.16 FOR REQUIRED FIXTURES, AND CIRCUITING.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  