| 2009-09-02 10:19:03 | FAILED |
| | |
| | 1) REPEAT COMMENT - THE PLANS SHALL SHOW THE GENERATOR |
| | AND ALL DIMENSIONS AND SETBACKS TO SCALE FROM THE |
| | ADJACENT PROPERTY LINE, THE WALL, THE LANDSCAPE AND THE |
| | PARKING AREA. THE EXISTING AND NEW LAYOUT PLANS SHOW |
| | DIFFERENT DIMENSIONS THAN THE BOB BELL SITE PLAN AND |
| | THE ELEVATION PLAN. THERE IS A TWO (2) FOOT |
| | DISCREPANCY. |
| | |
| | 2) REPEAT COMMENT - THE SITE PLAN SHOWS 12 FEET FROM |
| | THE WALL TO THE HANDICAP PARKING SPACE. THE LAYOUT |
| | DRAWINGS SHOW 10 FEET FROM THE WALL TO THE HANDICAP |
| | PARKING SPACE. ALL PLANS AND DRAWINGS NEED TO SHOW SAME |
| | AND ACCURATE DIMENSIONAL CONDITIONS. |
| | |
| | 3) REPEAT COMMENT - SHOW THE SCREEN HEDGE ON THE |
| | SUBMITTED PLANS. |
| | |
| | 4) THE NEW WALL TO THE EAST OF THE GENERATOR IS |
| | REQUIRED TO BE ON THE WEST SIDE OF THE EXISTING PALM |
| | LANDSCAPE ISLAND. THE MATERIAL OF THE NEW WALL SHALL |
| | COMPLY WITH ANY COMBUSTIBILITY RATINGS FOR THE REQUIRED |
| | LOCATION. |
| | |
| | 5) NOTE - THE GENERATOR PERMIT WILL NOT BE APPROVED |
| | UNTIL THE WALL/FENCE AND HEDGE PERMIT IS APPROVED. |
| | FENCE PERMIT NO. 09050324 DID NOT PASS ON INITIAL |
| | REVIEW. PLEASE INCLUDE THE FENCE RESUBMITTAL WITH THIS |
| | PERMIT. |
| | |
| | 6) THE GENERATOR WILL NOT RECEIVE A CERTIFICATE OF |
| | COMPLETION UNTIL THE WALL/FENCE AND HEDGE ARE |
| | INSTALLED. |
| | |
| | 7) NOTE - THE EXISTING LANDSCAPE TO THE EAST OF THE |
| | PROPOSED GENERATOR SHALL NOT BE REMOVED. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |