| 2009-07-24 13:06:34 | |
| | ** DENIED REVIEW. ** |
| | |
| | 1) NOTE: SITE PLANS DO NOT SHOW DIMENSIONS, DISTANCES |
| | LOCATIONS OF ALL EQUIPMENT ETC AS PREVIOUSLY NOTED. |
| | 110.26 ETC |
| | |
| | 2) NOTE: THE PLANS CONTAIN INSUFFICIENT DETAIL FOR |
| | SLABS FOR STRENGTH AND STABILITY SEE BUILDING REVIEW |
| | NOTES ALSO. |
| | IN THE SETS OF PLANS SUBMITTED SLAB IS SHOWN AS 4INCHES |
| | OR WHAT APPEARS TO BE 4INCHES ON SOME LOCATIONS AND |
| | 8INCHES ON OTHER LOCATIONS SUCH AS THE ELECTRICAL |
| | RISER. |
| | THE CONDUITS ON TRANSFER PANEL SLAB SHOWS 8-3INCH |
| | CONDUITS WHERE RISER INDICATES 3-4INCH CONDUITS. |
| | |
| | STEEL LAYOUT AROUND CONDUITS WITH SLAB DOES NOT PROVIDE |
| | STRENGTH AND STABILITY AS SHOWN. SEE TECHNICAL BUILDING |
| | REVIEW NOTES. |
| | |
| | COORDINATION BETWEEN SLAB INFORMATION AND OTHER DETAILS |
| | IS NEEDED. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |