Plan Review Notes
Plan Review Notes For Permit 09030017
Permit Number 09030017
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-24 13:06:34 
 ** DENIED REVIEW. **
  
 1) NOTE: SITE PLANS DO NOT SHOW DIMENSIONS, DISTANCES
 LOCATIONS OF ALL EQUIPMENT ETC AS PREVIOUSLY NOTED.
 110.26 ETC
  
 2) NOTE: THE PLANS CONTAIN INSUFFICIENT DETAIL FOR
 SLABS FOR STRENGTH AND STABILITY SEE BUILDING REVIEW
 NOTES ALSO.
 IN THE SETS OF PLANS SUBMITTED SLAB IS SHOWN AS 4INCHES
 OR WHAT APPEARS TO BE 4INCHES ON SOME LOCATIONS AND
 8INCHES ON OTHER LOCATIONS SUCH AS THE ELECTRICAL
 RISER.
 THE CONDUITS ON TRANSFER PANEL SLAB SHOWS 8-3INCH
 CONDUITS WHERE RISER INDICATES 3-4INCH CONDUITS.
  
 STEEL LAYOUT AROUND CONDUITS WITH SLAB DOES NOT PROVIDE
 STRENGTH AND STABILITY AS SHOWN. SEE TECHNICAL BUILDING
 REVIEW NOTES.
  
 COORDINATION BETWEEN SLAB INFORMATION AND OTHER DETAILS
 IS NEEDED.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  