Plan Review Notes
Plan Review Notes For Permit 09030017
Permit Number 09030017
Review Stop B
Sequence Number 2
Notes
Date Text
2009-08-06 08:54:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 3. PROVIDE A DETAIL FOR THE CONCRETE SLAB, FBC1603.1.
  
 THE DETAIL IS LABELED "NEW PAD FOR TRANSFER PANEL." TWO
 CONCRETE PADS ARE SHOWN ON THE SITE PLAN. I WAS UNABLE
 TO LOCATE A DETAIL FOR THE GENERATOR PAD. THE DETAIL
 PROVIDED IS NOT CLEAR; NO MINIMUM THICKNESS SHOWN. HOW
 WILL THE CONDUIT AFFECT STRUCTURAL INTEGRITY?
 FBC1604.1, PLEASE DEMONSTRATE THAT THE EQUIPMENT WILL
 RESIST OVERTURNING/SLIDING.
  
 4. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 NOT ADDRESSED. PLEASE NOTE THAT, BASED ON AERIALS, THIS
 APPEARS TO BE EXPOSURE C (NOTE THAT DEFINITION HAS
 CHANGED EFFECTIVE MARCH 1, 2009). FBC1609, ASCE7-05.
  
 5. SPECIFY ANCHORING TO SLAB; PROVIDE LENGTH, DIAMETER,
 AND TYPE OF ANCHOR PROPOSED.
  
 NO LENGTH WAS SPECIFIED. MANUFACTURER HAS A DIAMETER
 AND TOTAL NUMBER RECOMMENDATION ONLY. HAS THE
 MANUFACTURER TAKEN INTO ACCOUNT THE WIND DESIGN
 CRITERIA FOR OUR AREA?
  
  