| 2009-04-02 09:25:26 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT SITE ELECTRICAL PLANS WHICH ARE |
| | DETAILED SHOWING THE LOCATION WITH ALL DIMENSIONS. THIS |
| | INCLUDES EXACT DISTANCES FROM ALL SURROUNDING WALLS |
| | ETC. |
| | PLEASE KNOW AT THIS TIME BASED ON ZONING COMMENTS THERE |
| | MAY BE A NEED FOR OTHER COMMENTS ONCE WALLS OR |
| | SCREENING IS INSTALLED. PLEASE SEE OTHER COMMENTS BELOW |
| | WITH RESPECT TO DISCONNECTING MEANS. |
| | 110.26. |
| | |
| | 2) NOTE: PLEASE PLACE ALL PLANS, SITE PLANS, AND |
| | SPECIFICATIONS INTO TWO NEAT SETS FOR REVIEW. ALL PLANS |
| | AND SHEETS ARE LOOSE PLEASE ATTACH SHEETS INTO SETS. |
| | |
| | 3) NOTE: THE RISER SHOWING EXISTING CONDITIONS |
| | INDICATES AN EQUIPMENT GROUNDING CONDUCTOR FROM FPL TO |
| | THE FIRST MEANS OF DISCONNECT. |
| | THE REVISED PROPOSED RISER DOES NOT INDICATE ANY |
| | CONDUCTORS FOR THE LINE SIDE OF MAIN. |
| | 250.6,250.24 |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW PROPOSED SE RATED ATS. AS NO |
| | INFORMATION WAS SUBMITTED IT IS NOT POSSIBLE TO REVIEW. |
| | PLEASE BE SURE TO SEE 230.76, 230.79, 230.70,71 AND |
| | 110.9 FOR EQUIPMENT REQUIREMENTS. |
| | |
| | 5) NOTE: PLEASE BE SURE TO SEE COMMENTS FROM ALL OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |