Plan Review Notes
Plan Review Notes For Permit 09030017
Permit Number 09030017
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-02 09:25:26** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT SITE ELECTRICAL PLANS WHICH ARE
 DETAILED SHOWING THE LOCATION WITH ALL DIMENSIONS. THIS
 INCLUDES EXACT DISTANCES FROM ALL SURROUNDING WALLS
 ETC.
 PLEASE KNOW AT THIS TIME BASED ON ZONING COMMENTS THERE
 MAY BE A NEED FOR OTHER COMMENTS ONCE WALLS OR
 SCREENING IS INSTALLED. PLEASE SEE OTHER COMMENTS BELOW
 WITH RESPECT TO DISCONNECTING MEANS.
 110.26.
  
 2) NOTE: PLEASE PLACE ALL PLANS, SITE PLANS, AND
 SPECIFICATIONS INTO TWO NEAT SETS FOR REVIEW. ALL PLANS
 AND SHEETS ARE LOOSE PLEASE ATTACH SHEETS INTO SETS.
  
 3) NOTE: THE RISER SHOWING EXISTING CONDITIONS
 INDICATES AN EQUIPMENT GROUNDING CONDUCTOR FROM FPL TO
 THE FIRST MEANS OF DISCONNECT.
 THE REVISED PROPOSED RISER DOES NOT INDICATE ANY
 CONDUCTORS FOR THE LINE SIDE OF MAIN.
 250.6,250.24
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED SE RATED ATS. AS NO
 INFORMATION WAS SUBMITTED IT IS NOT POSSIBLE TO REVIEW.
 PLEASE BE SURE TO SEE 230.76, 230.79, 230.70,71 AND
 110.9 FOR EQUIPMENT REQUIREMENTS.
  
 5) NOTE: PLEASE BE SURE TO SEE COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  