| Plan Review Notes For Permit 09030005 |
| Permit Number |
09030005 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-03-04 14:01:39 | 2007 W/2008 REVISIONS | | | RE-ROOF | | | | | | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED | | | ROOFING SYSTEM IS TOO LOW FOR THE PERIMETER AND | | | CORNERS. SUBMIT TWO COPIES OF ENHANCED FASTENING | | | REQUIREMENTS FOR THE PERIMETER AND CORNER AREAS AS | | | CALCULATED IN COMPLIANCE WITH RAS 117 AS REQUIRED BY | | | GENERAL LIMITATION #7 ON PAGE 18 OF NOA 07-0730.03. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|