| 2009-03-09 13:56:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. DECLARE GOVERNING CODE. |
| | |
| | 2. DECLARE WIND DESIGN CRITERIA FBC R301. |
| | |
| | 3. DRYWALL FASTENING (SCREW LENGTH) TO COMPLY WITH FBC |
| | R702.3.6. |
| | |
| | 4. PROPOSED CONSTRUCTION IS TO RESIST WIND LOADS. |
| | STRAPS AT TOP, AROUND WINDOWS, NOT SHOWN. |
| | |
| | 5. THE DETAIL PROVIDED SHOWS A FRAME WALL AND A TIE |
| | BEAM. THE DETAIL DOES NOT SHOW ENOUGH INFORMATION TO |
| | SHOW SCOPE OF WORK. SEE FBC*106, PLANS ARE TO BE |
| | ARCHITECTURAL QUALITY AND TO SHOW SCOPE AND NATURE OF |
| | WORK. PROVIDE A PLAN AND OTHER SECTIONS TO CLEARLY SHOW |
| | WORK PROPOSED. FOR INSTANCE, PLAN SHOWS TIE BEAM BUT |
| | NOT HOW THIS TIE BEAM RELATES TO PROPOSED WORK. |
| | |
| | 6. NO INSULATION IS SHOWN, FBC13. WINDOWS ARE NOT |
| | SHOWN; DESCRIPTION STATES THIS IS A BAY WINDOW BUT NO |
| | WINDOW FRAMING DETAIL PROVIDED. THE DETAIL PROVIDED |
| | DOES NOT SHOW SCOPE OF WORK; PLEASE REVISE PLANS. |
| | |
| | 7. SHOW COMPLIANCE WITH FBC704.1, INSPECTION FOR |
| | TERMITES. |
| | |
| | |