Plan Review Notes
Plan Review Notes For Permit 09020632
Permit Number 09020632
Review Stop P
Sequence Number 1
Notes
Date Text
2009-03-12 09:54:43DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
  
 1. SHT A1.02 ACCESSIBILITY NOTE STATES "THE DRAIN AND
 WATER SUPPLY CONNECTIONS ALLOW THE UNIT TO BE SHIFTED
 IF NECESSARY TO ACCOMODATE THE REQUIRED FLOOR
 CLEAARANCES PER FACBC" PLEASE SUBMIT A DETAIL & MANUF.
 SPECIFICATIONS FOR THE DRAIN AND WATER SUPPLIES THAT
 INDICATES HOW THIS WORKS AND TO SHOW APPROVAL BY A
 THIRD PARTY TESTING & CERTIFICATION. SECTIONS 106.1.2 &
 303.4.
  
 2. SUBMIT MANUF. SEPCIFICATIONS FOR THE SINK. THE SINK
 SHALL MEET ASME A112.19.3M-87(R1996) STANDARD.
  
 3. SHT P1.01 NOTE STATES "REFER TO ATTACHED CUT SHEET"
 FOR PREFABRICATED KITCHEN COUNTER WITH RANGE,
 REFRIGERATOR, SINK, DISH WASHER ETC. CUT SHEET NOT
 ATTACHED. PLEASE SUBMIT THE MANUF. SPECIFICATION
 SHEETS. SECTIONS 106.1.2 & 303.4.
  
 4. SHT P1.01 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE OFFSETS SHOWN ON THE FLOOR PLAN ARE
 NOT SHOWN ON THE RISER DIAGRAM AND THE RISER SHOWS TWO
 TRAPS WHERE AS THE FLOOR PLAN SHOWS ONE TRAP. THE RISER
 DIAGRAM SHOWS A VENT AT THE SINK AREA THAT IS A DRY
 HORIZONTAL VENT WHICH IS NOT APPROVED AND NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1,
 905.3 & 905.4.
  
 5. SHT P1.01 WATER ISOMETRIC RISER DIAGRAM SHOWS AIR
 CHAMBERS AT THE SINK. AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE. SECTION 604.9 & PDI-WH 201. SECOND NOTE
 ONE INDICATES WATER HAMMER ARRESTORS ON THE HOT & COLD
 LINES BUT ONLY THE HOT LINE AT THE DISH WASHER IS
 SHOWING A WATER HAMMER ARRESTOR. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved