| 2009-04-07 10:19:21 | |
| | |
| | APPLICATION #09020628 ELECTRICAL PLAN REVIEW |
| | 400 S. FLAGLER DRIVE 3/27/09 |
| | WEST PALM BEACH, FL. |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED ON THE PLAN. |
| | |
| | 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND NRTL |
| | LISTING FOR ALL LUMINAIRES, BOLLARDS, POLES AND UTILITY |
| | PEDESTALS. |
| | |
| | 3} ALL SERVICES MUST COMPLY WITH 230.95 GROUND-FAULT |
| | PROTECTION OF EQUIPMENT |
| | GROUND-FAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED |
| | FOR SOLIDLY GROUNDED WYE ELECTRICAL SERVICES OF MORE |
| | THAN 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS |
| | PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000 |
| | AMPERES OR MORE. THE GROUNDED CONDUCTOR FOR THE SOLIDLY |
| | GROUNDED WYE SYSTEM SHALL BE CONNECTED DIRECTLY TO |
| | GROUND WITHOUT INSERTING ANY RESISTOR OR IMPEDANCE |
| | DEVICE. |
| | THE RATING OF THE SERVICE DISCONNECT SHALL BE |
| | CONSIDERED TO BE THE RATING OF THE LARGEST FUSE THAT |
| | CAN BE INSTALLED OR THE HIGHEST CONTINUOUS CURRENT TRIP |
| | SETTING FOR WHICH THE ACTUAL OVERCURRENT DEVICE |
| | INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE |
| | ADJUSTED. MAKE NOTE OF THIS ARTICLE ON SHEET E-300, OR |
| | SHEETS THAT THE SERVICE RISER DIAGRAMS ARE ON IF MOVED |
| | FROM THAT SHEET. |
| | |
| | 4} THE LOCATION OF THE SERVICES WILL REQUIRE A |
| | DISCONNECT PER 225.31 & 32. LOCATE ALL ON THE PLANS. |
| | |
| | 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 555.12 NEC. |
| | THE ???LOAD SCHEDULE??? ON SHEET E-300 DOES NOT |
| | INDICATE HOW THE DEMAND LOAD WAS CALCULATED. |
| | |
| | 6} THE NOTE REGARDING THE 480 VOLT 3 PHASE FEEDER ON |
| | SHEET E-103 INCORRECTLY STATES #210G FOR THE EQUIPMENT |
| | GROUND. SEE 250.122 FOR SIZING. |
| | |
| | 7} PER NFPA 303-2000, ARTICLE 3.3.1 |
| | A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF |
| | THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN |
| | THE MARINA OR BOATYARD. INDICATE THE LOCATION ON THE |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |