Plan Review Notes
Plan Review Notes For Permit 09020612
Permit Number 09020612
Review Stop G
Sequence Number 1
Notes
Date Text
2009-03-06 14:22:40DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 RESIDENTIAL
  
 A. THE FOLLOWING CORRECTIONS ARE REQUIRED FOR A GAS
 PERMIT:
  
 1. GAS ISOMETRIC RISER SHOWS A REGULATOR DOWNSTREAM OF
 THE METER, THEN DOWNSTREAM OF THE REGULATOR IS A GAS
 LINE TO THE TANKLESS WATER HEATER WITH ANOTHER GAS
 REGULATOR. PER TABLE G2413.4(1) MAXIMUM 200,000 BTU @
 20 FEET ALLOWED ON 3/4" SCHEDULE 40. 221,000 BTU IS
 INDICATED AFTER THE FIRST REGULATOR. PLEASE CLARIFY
 WHERE THE TANKLESS WATER HEATER IS CONNECTING TO THE
 GAS PIPING.
  
 2. A LISTED SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION
 G2420.5. A UNION IS REQUIRED AT THE FIRST REGULATOR TO
 ENABLE THE REGULATOR TO BE CHANGED/SERVICED. PLEASE
 SHOW THE SHUT OFF VALVE AND UNION ON ISOMETRIC.
  
 3. THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE GAS SYSTEM IS REQUIRED ON EACH SET OF
 PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  