| Date |
Text |
| 2009-03-06 14:22:40 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 RESIDENTIAL |
| | |
| | A. THE FOLLOWING CORRECTIONS ARE REQUIRED FOR A GAS |
| | PERMIT: |
| | |
| | 1. GAS ISOMETRIC RISER SHOWS A REGULATOR DOWNSTREAM OF |
| | THE METER, THEN DOWNSTREAM OF THE REGULATOR IS A GAS |
| | LINE TO THE TANKLESS WATER HEATER WITH ANOTHER GAS |
| | REGULATOR. PER TABLE G2413.4(1) MAXIMUM 200,000 BTU @ |
| | 20 FEET ALLOWED ON 3/4" SCHEDULE 40. 221,000 BTU IS |
| | INDICATED AFTER THE FIRST REGULATOR. PLEASE CLARIFY |
| | WHERE THE TANKLESS WATER HEATER IS CONNECTING TO THE |
| | GAS PIPING. |
| | |
| | 2. A LISTED SHUT OFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION |
| | G2420.5. A UNION IS REQUIRED AT THE FIRST REGULATOR TO |
| | ENABLE THE REGULATOR TO BE CHANGED/SERVICED. PLEASE |
| | SHOW THE SHUT OFF VALVE AND UNION ON ISOMETRIC. |
| | |
| | 3. THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | DESIGNING THE GAS SYSTEM IS REQUIRED ON EACH SET OF |
| | PLANS. SECTION 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |