| 2009-05-20 16:00:26 | REVISION DENIED |
| | REFERENCE: |
| | FBC-2004 RESIDENTIAL |
| | FBC-2004 FUEL GAS |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE ISOMETRIC INDICATES 1 FT FROM THE |
| | METER TO THE HORIZONTAL UNDERGROUND P.E. PIPE. THE |
| | MINIMUM BURIAL DEPTH FOR UNDERGROUND PIPE IS 1 FT. |
| | PLEASE INDICATE THE MEASUREMENT FROM THE GROUND TO THE |
| | OUTLET OF THE METER. SECTION G2415.9, (404.9). |
| | |
| | 2. THE ISOMETRIC SHOWS A 3/4" TO 1/2" REDUCER AT GROUND |
| | LEVEL. THE PIPING SHALL BE FULL SIZE THRU THE SHUT OFF |
| | VALVE. TABLE 402.4(20). |
| | |
| | 3. THE ISOMETRIC SHOW THE PIPING TO BE 3/4". PER TABLE |
| | 402.4(20) FOR 20 FT THE MINIMUM PIPE SIZE FOR 294,000 |
| | BTU SHALL BE 1". |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |