| 2009-04-14 10:01:40 | *****UNSAT***** |
| | |
| | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK |
| | OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 2. DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE BUILDING |
| | ON THE APPROPIATE EXTERIOR ELEVATION VISIBLE FROM |
| | BELVEDERE ROAD. AS PER WEST PALM BEACH CODE, THE |
| | ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND |
| | NO LESS THAN 1" IN WIDTH/STROKE. IN THE EVENT THAT THE |
| | VISIBILITY OF THE ADDRESS IS NOT PLAINLY VISIBLE FROM |
| | THE ROADWAY, A MARKEE AND/OR SIGN POST WITH THE ADDRESS |
| | WILL BE REQUIRED IN ADDITION TO THE ADDRESS ON THE |
| | BUILDING. |
| | |
| | 3. LANDSCAPING AND THE LIKE SUCH OPERATIONS SHALL NOT |
| | OBSTRUCT A FIRE HYDRANT OR FIRE PROTECTION APPLIANCE |
| | AND HINDER OR PREVENT ITS IMMEDIATE USE BY THE FIRE |
| | PERSONNEL. SUCH FIRE HYDRANT OR FIRE PROTECTION |
| | APPLIANCE SHALL BE MAINTAINED READILY VISIBLE AT ALL |
| | TIMES. |
| | |
| | 4. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER LOCATED INSIDE THE STRUCTURE. |
| | |
| | 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 6. BASED ON THE ASSUMPTION THAT THIS STRUCTURE IS A |
| | STORAGE OCCUPANCY, CLASSIFY THE MATERIALS TO BE STORED |
| | AS LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD. |
| | |
| | 7. ON SHEET A04, A SMOKE DETECTOR (SD) IS SHOWN IN THE |
| | ELECTRICAL FLOOR PLAN. IS THIS DEVICE A SMOKE DETECTOR |
| | OR A SMOKE ALARM (SA)? PLEASE BE ADVISED THAT A SMOKE |
| | DETECTOR IS TIED TO THE BUILDING'S FIRE ALARM SYSTEM |
| | WHEREAS A SMOKE DETECTOR ALERTS THE OCCUPANT(S) ONLY |
| | AND IS NOT TIED INTO A FIRE ALARM SYSTEM. |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHER E EACH COMMENT WAS ADDRESSED. |
| | |
| | CAPT MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |