2009-02-26 14:19:45RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PERMIT APPLICATION CALLS FOR REPLACEMENT OF JALOUSIE
 WINDOWS WITH "IMPACT" FRENCH DOORS WITH SIDELITES.
 PRODUCT APPROVAL NOA 06-0629.01 SUBMITTED IS FOR
 "NON-IMPACT" DOORS. PROVIDE PRODUCT APPROVAL FOR IMPACT
 DOORS AS SPECIFIED ON PERMIT APPLICATION.
  
 2- PROVIDE DETAIL/SPECIFICATIONS SHOWING HOW INSTALLING
 THE BUCKS AND HEADER TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE. PERMIT APPLICATION SAYS "INSTALL
 BUCKS AND HEADER TO COMPLY W/ CODE". THIS DOESN'T
 PROVIDE ANY INFORMATION ON PROPOSED INSTALLATION.
 NOTE: CLARIFY WHY INSTALLING NEW HEADER IF DOORS ARE
 GOING TO BE INSTALLED ON EXISTING OPENING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER