| | APPLICATION #09020560 ELECTRICAL PLAN REVIEW |
| | 836 ALMERIA ROAD #836-840 3/5/09 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THIS COMMENT WAS PART OF THE PREVIOUS REVIEW |
| | 1} SEE 230.2 NUMBER OF SERVICES |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE*** FROM THE PARTIAL RISER SUBMITTED IT |
| | CANNOT BE DETERMINED IF COMPLIANCE WITH THIS ARTICLE IS |
| | MET. |
| | |
| | NEW COMMENTS GENERATED BY THE RISER CHANGE. |
| | |
| | 2} THE CONDUCTORS FROM THE DISCONNECT LOCATION NOW |
| | SHOWN ARE RUNNING OVERHEAD AND POSSIBLY PANEL "B" IS |
| | BEING FEED THROUGH BUILDING "A" IN VIOLATION OF 230..3 |
| | NEC |
| | |
| | 3} THE FEED FROM THE DICONNECTS TO THE PANEL MUST |
| | CONTAIN AN EQUIPMENT GROUND PER 250.122. NEC |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |