| 2009-03-12 10:43:46 | RE-ROOF BUILDING REVIEW SECOND CHECKLIST. |
| | |
| | THE FOLLOWING ITEMS WERE NOT ADDRESSED FROM THE FIRST |
| | CHECKLIST: |
| | |
| | 1- A) CONTRACTOR TO SELECT ON PRODUCT APPROVAL |
| | SUBMITTED THE SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED (REPEAT COMMENT. THIS WAS NOT DONE). |
| | CONTRACTOR WROTE "GAF 1-1/4 RING SHANK" NEXT TO THIS |
| | COMMENT, BUT THIS DOESN'T ADDRESS THE QUESTION ASKED. |
| | |
| | B) INDICATE SPECIFIC BASE SHEET FASTENING OPTION. |
| | REPEAT COMMENT. THIS WAS NOT DONE). |
| | |
| | ***NOTE: KEEP IN MIND THAT APPROVED ASSEMBLY IS FOR AN |
| | INSULATED ASSEMBLY SINCE PERMIT APPLICATION CALLS FOR |
| | INSULATION BOARD TO BE INSTALLED. |
| | |
| | 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA 07-0111.03 SUBMITTED |
| | (REPEAT COMMENT. THIS WAS NOT DONE). CONTRACTOR WROTE " |
| | FIELD -47.3PSF, PER. -79.4PSF, CORNER -119.5PSF" NEXT |
| | TO THE COMMENT, BUT THIS DOESN'T ADDRESS THE QUESTION |
| | ASKED. THESE ARE JUST THE DESIGN PRESSURES THAT NEED TO |
| | BE RESISTED. STILL NEED TO PROVIDE INFORMATION SHOWING |
| | HOW THE FASTENERS WILL BE INSTALLED TO MEET THOSE |
| | DESIGN PRESSURES. |
| | |
| | 3- PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT. THE ONE |
| | THAT WAS PROVIDED IS EXPIRED BECAUSE IT WAS RECORDED ON |
| | 12/01/2008. NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 |
| | DAYS IF WORK IS NOT STARTED (SEC. 713.13 FLORIDA |
| | STATUTE). NEED TO PROVIDE RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |