| 2009-02-27 14:55:50 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 EXISTING BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SUBMIT AN ARCHITECTURAL QUALITY FLOOR PLAN SHOWING |
| | THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN SO |
| | THE EXTENT OF WORK CAN BE VERIFIED. SECTION 106.1.2 |
| | (MORE INFORMATION REQUIRED). SHOW THE LOCATION OF ALL |
| | FIXTURES, SEATING, TOILET ROOM(S), LOCATION OF PROPOSED |
| | GREASE TRAP, SQUARE FOOTAGE OF THE SPACE, SANITARY AND |
| | WATER PIPING ETC. PER ARTICLE III SECTION 90-124(7)(B) |
| | THE GREASE INTERCEPTOR/TRAP CAN NOT BE LOCATED IN THE |
| | FOOD PREPARATION AREA. |
| | |
| | 2. INDICATE ON THE PLANS THE CODE CRITERIA ON WHICH THE |
| | DESIGN IS BASED ON. (FBC-2004 W/2007 REVISIONS). |
| | SECTION 106.1.1. |
| | |
| | 3. INDICATE ON THE PLANS THE LEVEL OF ALTERATION PER |
| | CHAPTER 3 OF THE EXISTING BUILDING CODE. |
| | |
| | 4. THE GREASE INTERCEPTOR/TRAP SHALL BE SIZED BY THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH BY PHONE (561) |
| | 822-2271, BY FAX (561) 822-2279 OR BY E-MAIL |
| | [email protected]. ARTICLE III SECTION 90-124(7). |
| | |
| | 5. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| | VALVES, AND (IF REQUIRED BY 604.9), WATER HAMMER |
| | ARRESTORS AS WELL AS POINT OF CONNECTION. SECTIONS |
| | 106.3.5.1.3 AND 701.1. |
| | |
| | 6. PLEASE INDICATE ON THE APPLICATION IS THIS IS A |
| | CHANGE OF OCCUPANCY AND THE SQUARE FOOTAGE OF THE |
| | SPACE. SECTION 105.1. |
| | |
| | 7. 104.6.5 BUILDING PERMIT VALUATION. IF |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, AL- |
| | TERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES |
| | AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| | CLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION FOR BUILDINGS AND |
| | SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| | ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| | (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| | AND PROFIT, EXCLUDING ONLY LAND VALUE. -- THE |
| | INSTALLATION OF A 3 COMPARTMENT SINK, A HAND SINK, A |
| | MOP SINK AND A GREASE TRAP WITH ALL THE REQUIRED WASTE |
| | & WATER PIPING, OPENING UP THE FLOOR, PATCHING THE |
| | FLOOR AS WELL AS THE COST OF THE FIXTURES FOR $2,400 |
| | SEEMS TO BE UNDERESTIMATED. PLEASE SUBMIT A VALUE THAT |
| | WOULD BE MORE IN LINE WITH THE WORK BEING DONE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |