Plan Review Notes
Plan Review Notes For Permit 09020538
Permit Number 09020538
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-27 14:55:50DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 EXISTING BUILDING
 CITY WPB MUNICIPAL CODE
  
 1. SUBMIT AN ARCHITECTURAL QUALITY FLOOR PLAN SHOWING
 THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN SO
 THE EXTENT OF WORK CAN BE VERIFIED. SECTION 106.1.2
 (MORE INFORMATION REQUIRED). SHOW THE LOCATION OF ALL
 FIXTURES, SEATING, TOILET ROOM(S), LOCATION OF PROPOSED
 GREASE TRAP, SQUARE FOOTAGE OF THE SPACE, SANITARY AND
 WATER PIPING ETC. PER ARTICLE III SECTION 90-124(7)(B)
 THE GREASE INTERCEPTOR/TRAP CAN NOT BE LOCATED IN THE
 FOOD PREPARATION AREA.
  
 2. INDICATE ON THE PLANS THE CODE CRITERIA ON WHICH THE
 DESIGN IS BASED ON. (FBC-2004 W/2007 REVISIONS).
 SECTION 106.1.1.
  
 3. INDICATE ON THE PLANS THE LEVEL OF ALTERATION PER
 CHAPTER 3 OF THE EXISTING BUILDING CODE.
  
 4. THE GREASE INTERCEPTOR/TRAP SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH BY PHONE (561)
 822-2271, BY FAX (561) 822-2279 OR BY E-MAIL
 [email protected]. ARTICLE III SECTION 90-124(7).
  
 5. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND (IF REQUIRED BY 604.9), WATER HAMMER
 ARRESTORS AS WELL AS POINT OF CONNECTION. SECTIONS
 106.3.5.1.3 AND 701.1.
  
 6. PLEASE INDICATE ON THE APPLICATION IS THIS IS A
 CHANGE OF OCCUPANCY AND THE SQUARE FOOTAGE OF THE
 SPACE. SECTION 105.1.
  
 7. 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE. -- THE
 INSTALLATION OF A 3 COMPARTMENT SINK, A HAND SINK, A
 MOP SINK AND A GREASE TRAP WITH ALL THE REQUIRED WASTE
 & WATER PIPING, OPENING UP THE FLOOR, PATCHING THE
 FLOOR AS WELL AS THE COST OF THE FIXTURES FOR $2,400
 SEEMS TO BE UNDERESTIMATED. PLEASE SUBMIT A VALUE THAT
 WOULD BE MORE IN LINE WITH THE WORK BEING DONE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  